| 2003-12-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) ROUTE PLANS TO THE DEPT. OF BUSINESS |
| | REGULATION HOTEL AND RESTURANT DIV. FOR |
| | REVIEW PRIOR TO RESUBMITTING PLANS. |
| | 2) CONTACT RODNEY COMPO, INDUSTRIAL PRE- |
| | TREATMENT, ENVIRONMENTAL COMPLIANCE MGR. |
| | FOR SIZING OF GREASE INTECPTOR. WASTE |
| | ORD. 2938-96 - (561) 837-4074 |
| | 3) SHT P1.1 PLUMBING NOTES: #1 CODE |
| | ADOPTED AND IN AFFECT IS THE FLORIDA |
| | BUILDING CODE PLUMBING NOT THE BOCA CODE |
| | AMEND REFERNCE. |
| | 4) SHT P1.1 PLUMBING NOTES: #3 AIR CHAM- |
| | BERS ARE NOT APPROVED. DELETE REFERENCE. |
| | SEC 604.9 |
| | 5) SHT P1.1 GAS WATER HEATER DETAIL, THE |
| | DRAINAGE PIPING FROM THE P/T (RELIEF) |
| | VALVE SHALL DRAIN TO A FLOOR SINK OR A |
| | HUB DRAIN. FLOOR SINKS ARE NOT APPROVED |
| | INDIRECT WASTE RECEPTORS. SEC 802.3 - |
| | ALL OTHER INDIRECT WASTE SHALL DRAIN TO |
| | A FLOOR SINK. (IN KITCHEN FOOD PREP AREA |
| | ECT.) - ALSO SEE SHEET P1.2 |
| | 6) SHT P1.2 DOMESTIC WATER RISER, AIR |
| | CHAMBERS NOT APPROVED. 604.9 DELETE |
| | FROM RISER. WATER HAMMER ARRESTORS RE- |
| | QUIRED BY SECTION 604.9 SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING. PDI-WH 201 AND MANUF |
| | INSTALL. INSTRUCT. |
| | 7) FOLLOWING INFORMATION REQUIRED FOR |
| | GAS PERMIT. |
| | A. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES. |
| | B. TYPE OF GAS, (LP OR NATURAL) |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | G. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | H. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |