Notes
Date Text
2003-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION HOTEL AND RESTURANT DIV. FOR
 REVIEW PRIOR TO RESUBMITTING PLANS.
 2) CONTACT RODNEY COMPO, INDUSTRIAL PRE-
 TREATMENT, ENVIRONMENTAL COMPLIANCE MGR.
 FOR SIZING OF GREASE INTECPTOR. WASTE
 ORD. 2938-96 - (561) 837-4074
 3) SHT P1.1 PLUMBING NOTES: #1 CODE
 ADOPTED AND IN AFFECT IS THE FLORIDA
 BUILDING CODE PLUMBING NOT THE BOCA CODE
 AMEND REFERNCE.
 4) SHT P1.1 PLUMBING NOTES: #3 AIR CHAM-
 BERS ARE NOT APPROVED. DELETE REFERENCE.
 SEC 604.9
 5) SHT P1.1 GAS WATER HEATER DETAIL, THE
 DRAINAGE PIPING FROM THE P/T (RELIEF)
 VALVE SHALL DRAIN TO A FLOOR SINK OR A
 HUB DRAIN. FLOOR SINKS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. SEC 802.3 -
 ALL OTHER INDIRECT WASTE SHALL DRAIN TO
 A FLOOR SINK. (IN KITCHEN FOOD PREP AREA
 ECT.) - ALSO SEE SHEET P1.2
 6) SHT P1.2 DOMESTIC WATER RISER, AIR
 CHAMBERS NOT APPROVED. 604.9 DELETE
 FROM RISER. WATER HAMMER ARRESTORS RE-
 QUIRED BY SECTION 604.9 SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING. PDI-WH 201 AND MANUF
 INSTALL. INSTRUCT.
 7) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT.
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]