Plan Review Notes
Plan Review Notes For Permit 03110799
Permit Number 03110799
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-11 00:00:00DENIED:
 1. 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE THE FOLLOWING WITH HIS TITLE
 BLOCK:
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 2.PLEASE CLARIFY DUCT REFERENCED IN
 KEY NOTE 1.INIDCATE WHAT TYPE OF DUCT
 THIS IS AND WHY DOES IT RUN THROUGH THE
 ADJACENT TENANT WITH NO FIRE DAMPER
 INDICATED.
  
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR HOOD AND FIRE SUPPRESSION.PLEASE
 PROVIDE THE FOLLOWING INFORMAITON ON
 THE HOOD/GREASE DUCT FOR A REVIEW AT
 THIS TIME OR PROVIDE COMPLETE PLANS WITH
 HOOD PERMIT APPLICATION.
 1.INDICATE DUCT LAYOUT AND SIZING.
 2.AIR VELOCITY WITHIN DUCT SYSTEM
 SHALL BE NOT LESS THAN 1,500 & NOT
 GREATER THAN 2,500.
 3.CLEANOUTS REQUIRED AT CHANGE OF
 DIRECTION.
 4.INDICATE CLEARANCE TO COMBUSTIBLES.
 5.EXHAUST OUTLETS SHALL BE LOCATED
 NOT LESS THAN 10 FT HORIZONTALLY FROM
 PROPERTY LINES AIR INTAKE OPENINGS OR
 PARTS OF THE SAME OR CONTIGUOUS BUILDING
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.