| Date |
Text |
| 2003-12-11 00:00:00 | DENIED: |
| | 1. 61G1-16.004FL. ADMIN. CODE.PLANS |
| | PREPARED BY A REGISTERED ARCHITECT SHALL |
| | INCLUDE THE FOLLOWING WITH HIS TITLE |
| | BLOCK: |
| | - STATE DATE PREPARED |
| | - INCLUDE AN ORIGINAL SIGNATURE AND |
| | DATED SEAL |
| | - INCLUDE THE PRINTED NAME OF THE |
| | ARCHITECT SEALING THE PLANS |
| | |
| | 2.PLEASE CLARIFY DUCT REFERENCED IN |
| | KEY NOTE 1.INIDCATE WHAT TYPE OF DUCT |
| | THIS IS AND WHY DOES IT RUN THROUGH THE |
| | ADJACENT TENANT WITH NO FIRE DAMPER |
| | INDICATED. |
| | |
| | PLEASE NOTE ADDITIONAL PERMITS REQUIRED |
| | FOR HOOD AND FIRE SUPPRESSION.PLEASE |
| | PROVIDE THE FOLLOWING INFORMAITON ON |
| | THE HOOD/GREASE DUCT FOR A REVIEW AT |
| | THIS TIME OR PROVIDE COMPLETE PLANS WITH |
| | HOOD PERMIT APPLICATION. |
| | 1.INDICATE DUCT LAYOUT AND SIZING. |
| | 2.AIR VELOCITY WITHIN DUCT SYSTEM |
| | SHALL BE NOT LESS THAN 1,500 & NOT |
| | GREATER THAN 2,500. |
| | 3.CLEANOUTS REQUIRED AT CHANGE OF |
| | DIRECTION. |
| | 4.INDICATE CLEARANCE TO COMBUSTIBLES. |
| | 5.EXHAUST OUTLETS SHALL BE LOCATED |
| | NOT LESS THAN 10 FT HORIZONTALLY FROM |
| | PROPERTY LINES AIR INTAKE OPENINGS OR |
| | PARTS OF THE SAME OR CONTIGUOUS BUILDING |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |