| Date |
Text |
| 2003-12-16 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) 61G1-16.004FL. ADMIN. CODE.THE |
| | ARCHITECTURAL SHEETS MUST BE SIGNED, |
| | DATED AND SEALED BY KERMIT C. WHITE. |
| | |
| | 2) FBC 2405.2SHEET A1.1, KEY NOTE 2. |
| | THE VIEW PANEL IN THE NEW KITCHEN DOOR |
| | WILL BE A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS OR ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 3) FBC 11-5.1RESTAURANT SEATING.AT |
| | LEAST 5% OF THE SEATING SHALL BE |
| | ACCESSIBLE AND SHALL COMPLY WITH 11-4.32 |
| | WITH RESPECT TO CLEAR FLOOR SPACE, KNEE |
| | CLEARANCES AND TABLE HEIGHT.AMEND/ |
| | ANNOTATE THE PLANS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 4) FBC 11-5.2SERVICE BAR.A MINIMUM |
| | 60" LENGTH OF THE BAR SHALL BETWEEN 28" |
| | AND 34" ABOVE FINISHED FLOOR, TO COMPLY |
| | WITH 11-4.32.4, OR SERVICE SHALL BE |
| | AVAILABLE AT ACCESSIBLE TABLES WITHIN |
| | THE SAME AREA.AMEND/ANNOTATE THE PLANS |
| | TO DEMONSTRATE COMPLIANCE. |
| | |
| | 5)FBC 1010EXIT DISCHARGE.ANNOTATE |
| | THE PLANS TO CLARIFY WHAT KIND OF SPACE |
| | (ALLEY ETC) CORRIDOR 103 PROVIDES EXIT |
| | TO, THROUGH THE EXISTING DOORS. |
| | |
| | 6) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |