| Plan Review Notes For Permit 03110774 |
| Permit Number |
03110774 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-31 00:00:00 | ****************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE MISSING FOOTER STEEL | | | AS PART OF THE GROUNDING ELECTRODE | | | SYSTEM. 250.50 | | | | | | 2)NOTE: PLEASE SEE 210.52D/210.11C3, | | | BATH CIRCUITS TO BE 20A , #12. SHOWN AS | | | #14.15A. | | | | | | 3)NOTE: LOAD CALCULATIONS DO NOT | | | CORRELATE WITH LOADS. AHU/HEAT SHOWN | | | AS 7KW AND DOES NOT FIGURE @ 65%. | | | PLEASE VERIFY 7KW AND PLEASE ALSO SEE | | | OCP FOR AHU, SHOWN AS 2P-30A. PLEASE | | | SEE 424.3B | | | | | | 4)NOTE: PLEASE SEE MISSING OCP AND AWG | | | FOR OTHER APPLIANCES ON PANEL SCHEDULE. | | | (FRIG/WASHER ETC ) | | | | | | 5)NOTE: PLEASE SHOW LOCATION OF PANEL | | | AND SERVICE ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|