| Plan Review Notes For Permit 03110709 |
| Permit Number |
03110709 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-10 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03110709 | | | ADD: 4047 OKEECHOBEE BLVD SUITE 211 | | | CONT: HOBAN CONSTRUCTION | | | TEL: (561)631-0070 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ACTION: DENIED | | | 1) 1021.4 DOORS THAT SWING INTO AN EXIT | | | CORRIDOR SHALL BE RECESSED TO PREVENT | | | INTERFERENCE WITH CORRIDOR TRAFFIC; ANY | | | DOORS NOT RECESSED SHALL OPEN 180 DEGREE | | | TO STOP AGAINST THEWALL. | | | | | | 2)1005.4 EMERGENCY ESCAPE AND RESCUE | | | OPENINGS, | | | (2) EVERY ROOM OR SPACE GREATER THAN | | | 250 FT USED FOR CLASSROOM OR OTHER ED- | | | UCATIONAL PURPOSES OR NORMALLY SUBJECT | | | TO STUDENT OCCUPANCY, AND EVERY ROOM | | | SUBJECT TO CLIENT OCCUPNCY SHALL NOT | | | HAVE NOT LESS THAN ONE OUTSIDE WINDOW | | | FOR EMERGENCY RESCUE, SEE EXCEPTIONS: | | | 1) FIRE SPRINKLERS, GIVE LOCATION OF | | | THE EXISTING FIRE SPRINKLERS. | | | | | | 3)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | PROVIDE FLOOR PLAN OF THE TOTAL SCHOOL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|