| 2004-02-09 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 12/5/03: |
| | |
| | 3) FBC 13-103.1.2BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | NOTE: ONLY ONE COPY WAS SUBMITTED. |
| | SUBMIT A SECOND COPY. |
| | |
| | 4) SINGLE PLY MEMBRANE ROOFING PRODUCT |
| | APPROVAL.THE CORRESPONDING STATE |
| | APPROVAL COVER SHEET WITH REFERENCE # |
| | HAS BEEN PRINTED AND ATTACHED TO THE |
| | SUBMITTED MIAMI-DADE NOTICE OF |
| | ACCEPTANCE.MARK THE PRODUCT APPROVAL |
| | SHEETS, AS APPROPRIATE, TO IDENTIFY |
| | WHICH PRODUCT SYSTEM/OPTIONS/MATERIALS |
| | ARE BE USED. |
| | |
| | 5) FL. ADMIN CODE RULE 9B-72. |
| | A SEARCH AT THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | SHOWS NO MATCHING STATEWIDE PRODUCT |
| | APPROVAL FOR THE SUBMITTED ARCH ALUMINUM |
| | FIXED WINDOW WALL PRODUCT APPROVAL |
| | (NOA# 01-0329.02) OR CECO DOOR PRODUCTS' |
| | OUTSWING STEEL DOOR PRODUCT APPROVALS |
| | (NOA#'S 00-0315.03 & 01-0118.01). EITHER |
| | SPECIFY ALTERNATIVES THAT HAVE STATEWIDE |
| | APPROVAL OR APPLY FOR SITE SPECIFIC |
| | PRODUCT APPROVAL BY HAVING THE |
| | MANUFACTURER COMPLETE THE FORM |
| | 'APPLICATION FOR SITE SPECIFIC PRODUCT |
| | APPROVAL' (AVAILABLE FROM THIS OFFICE). |
| | |
| | 7) FBC 1606.1TRUSS ANCHOR WIND UPLIFT. |
| | AMEND SHEET S-1 TO SPECIFY THE ANCHOR |
| | FASTENERS REQUIRED TO ACHIEVE THE STATED |
| | UPLIFTS FOR THE SIMPSON H16 AND HUS26 |
| | TIES. |
| | |
| | 9) FBC 11-4.16.4SHEET A-5, REVISED |
| | GRAB BAR ON ACCESSIBLE W.C. DETAIL 11. |
| | THE GRAB BAR SHALL EXTEND AT LEAST 12" |
| | ON EACH SIDE OF THE W.C. CENTER LINE |
| | (REF. FIG. 29A) |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |