| Plan Review Notes For Permit 03110653 |
| Permit Number |
03110653 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) SHT A-1 TOILET ROOM 103, SHOW CLEAR | | | FLOOR SPACE AND TURNING AREA PER SECTION | | | 11-4.22.3 | | | 2) SHT P-1 KEYNOTE #2, SINK IN SACRISTY | | | SHALL DRAIN INTO SANITARY. DRYWELL NOT | | | APPROVED. SECTION 701.2 | | | 3) SIGNATURE REQUIRED ON SEAL OF ENGIN- | | | EER PER FAC 61G15-23.002(1) & FLA. STAT- | | | UTES. INITIALS NOT APPROVED PER FBPE & | | | BLDG. OFFICIAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|