| 2003-12-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| | AND A COPY SUBMITTED TO THIS OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| | TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| | |
| | 4) SUBMIT PRODUCT APPROVALS FOR THE |
| | NEW ROOF COVERING SYSTEM. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | |
| | 5) SUBMIT PRODUCT APPROVALS FOR THE |
| | WINDOWS AND EXTERIOR DOORS. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | |
| | 6) FBC 1606.2.5DESIGN WIND PRESSURES. |
| | THE PLANS SHALL BE AMENDED TO SHOW THE |
| | POSITIVE AND NEGATIVE DESIGN WIND |
| | PRESSURES ACTING ON THE WINDOWS, |
| | EXTERIOR DOORS AND ROOF COVERING, FOR |
| | CROSS-REFERENCE WITH THE PRODUCT |
| | APPROVALS TO ESTABLISH SUITABILITY OF |
| | THE SPECIFIED PRODUCTS. |
| | |
| | 7) FBC 1606.1TRUSS ANCHOR WIND UPLIFT. |
| | SHEET S-1, ROOF FRAMING PLAN SPECIFIES |
| | SIMPSON HU65 ANCHORS AT THE NEW TRUSSES. |
| | THIS IS NOT A VALID SIMPSON REFERENCE. |
| | AMEND THE PLAN. |
| | |
| | 8) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |