| 2004-04-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) FROM PREVIOUS REVIEW: CONTACT RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE, INDUST- |
| | RIAL PRETREATMENT FOR SIZING OF OIL/ |
| | WASTE INTERCEPTOR. WASTE ORD. #2938-96. |
| | (561) 837-4074. - RESPONSE NOTED BUT NOT |
| | SURE WHAT WAS REVISED. PLEASE CLARIFY. |
| | 2) CLARIFICATION OF RESPONSE CONCERNING |
| | THE WATER SUPPLY TO FOUNTAIN. PLEASE IN- |
| | DICATE IF THE WATER SUPPLY TO FOUNTAIN |
| | WILL BE DIRECT TO FOUNTAIN OR WILL IT BE |
| | FILLED BY HOSE FROM A HOSE BIBB. IF |
| | DIRECTLY TIED IN A BACKFLOW WILL BE RE- |
| | QUIRED ON THE SUPPLY LINE. |
| | 3) IRRIGATION SHEETS, A CERTIFICATE OF |
| | AUTHORIZATION NUMBER IS REQUIRED ON THE |
| | TITLE BLOCK PER FS 481.219(2)(3) |
| | 4) SHTS P2.1, P2.3, (DETAIL 7), & P3.1 |
| | THE TRIAGE SINK SHALL NOT DRAIN THROUGH |
| | THE WET VENTED HORIZONTAL DRAIN FOR THE |
| | BATHROOM FIXTURES. SECTION 909.1 THE |
| | SINK SHALL DISCHARGE DOWNSTREAM OF THE |
| | BATHROOM FIXTURES. |
| | 5) SHTS P2.1, & P3.1 (SANITARY RISER |
| | DIAGRAM), THE FLOOR DRAIN IN ROOM #145 |
| | BY THE COMPRESSOR REQUIRES A VENT. |
| | SECTION 901.2.1 |
| | 6) SHTS P2.1, P2.3 (DETAIL 5), & P3.1 |
| | SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN. FLOOR DRAIN OUTSIDE THE |
| | SHOWERS IS NOT SHOWN ON RISER DIAGRAM. |
| | 7) SHT 3.2 WATER RISER DIAGRAM. WATER |
| | HAMMER ARRESTORS REQUIRED BY SECTION |
| | 604.9 (AT WASH MACHINE, ICE MAKERS, AND |
| | DISH WASHER), OR ANY OTHER QUICK CLOSING |
| | VALVES SHALL BE SHOWN ON RISER DIAGRAM. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE |
| | NOT IN THE CEILING. PDI-WH 201 AND MANUF |
| | INSTALLATION INSTRUCTIONS. |
| | 8) SHT P3.2 GAS ISOMETRIC RISER DIAGRAM, |
| | 2" PIPE REQUIRED UP TO WHERE THE LINE TO |
| | THE STOVE/RANGE CONNECTS TO THE GAS MAIN |
| | (INFORMATIONAL - 1" MINIMUM REQUIRED TO |
| | WATER HEATER "2 - SHOWS 1-1/4" NOW). |
| | 9-ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |