| 2004-04-09 00:00:00 | 1) ELECTRONIC SWITCHES, CHANIN AND |
| | LOCK REQUIRED ON BACKFLOW DEVICE. |
| | NO CHANGE NOTED TO PAGE C-4.2. |
| | |
| | 2) DOOR 147A IS NOT RATED PER THE DOOR |
| | SCHEDULE. DOOR IS LOCATED IN RATED |
| | WALL THEREFORE AN OPENING PROTECTIVE |
| | IS REQUIRED. PLEASE REVISE PLANS |
| | AS NECESSARY. |
| | |
| | 3) PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR HANDRAILS AND GUARDRAILS SHALL |
| | MEET THE FLORIDA BUILDING CODE AND |
| | THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 4) THE ABOVE GROUND FUEL STORAGE TANK |
| | SHALL BE PROTECTED BY BOLLARDS TO |
| | PREVENT MECHANICAL DAMAGE, BE LABELED |
| | AS TO ITS DEISEL CONTENT, AND BE |
| | PLACARDED IN ACCORDANCE WITH NFPA |
| | 704. ALSO NO SMOKING SIGNS SHALL |
| | BE PROVIDED. |
| | |
| | 5) THE FIRE DEPARTMENT CONNECTION FOR |
| | THE FIRE SPRINKLER SYSTEM SHALL BE |
| | PROVIDED WITH CLEAR ACCESS AND BE |
| | PROVIDED WITH SEVEN FEET, SIX INCHES |
| | OF CLEARANCE. |
| | |
| | 6) WHAT PREVENTS THE GENERATOR EXHAUST |
| | FROM BACKFEEDING INTO THE AIR EXHAUST |
| | LOUVERS. |
| | |
| | 7) ALL SMOKE DETECTORS SHALL BE MOUNTED |
| | A MINIMUM OF THREE FEET FROM AIR |
| | CONDITIONER DIFFUSERS. |
| | |
| | 8) PLEASE CLEARLY IDENTIFY ALL |
| | EMERGENCY LIGHT FIXTURES ON THE PLAN. |
| | |
| | 9) THE OPENING FROM 50TH STREET SHOULD |
| | BE WIDER BECAUSE SERVICE VEHICLES WILL |
| | HAVE TO ENTER THOUGH THE SEPARATED |
| | OPENING. THESE INCLUDE SANITATION |
| | TRUCKS AND FUEL TRUCKS. THE DIVIDER |
| | SERVES NO REAL PURPOSE BUT WOULD |
| | PROVIDE A POTENTIAL FOR MISHAPS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |