| Date |
Text |
| 2003-12-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 FUEL GAS |
| | FLA. ADMIN. CODE |
| | FLA STATUTES |
| | |
| | 1) SHTS C-2.1 & C-4.1 WATER SERVICE IN- |
| | DICATES A PRESSURE VAC BREAKER ON THE |
| | WATER SERVICE. AN RPZ BACKFLOW IS REQ- |
| | UIRED. 608.13.2 |
| | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE, INDUSTRIAL PRETREATMENT FOR |
| | SIZING OF OIL/WATER INTECEPTOR. WASTE |
| | ORD. #2938-96. (561) 837-4074 |
| | 3) SHT L1 MORE INFORMATION REQUIRED ON |
| | THE FOUNTAIN. WILL THERE BE DRAINAGE OR |
| | WATER SUPPLIED TO THE FOUNTAIN? |
| | 4) SEPARATE PLANS/PERMIT REQUIRED FOR |
| | IRRIGATION. |
| | 5) SHT A2.4 EQUIPMENT & ACCESSORIES SHC- |
| | EDULE. CLAIRFY #42 GAS LINE OUTLET, IS |
| | THIS NATURAL GAS, OR A FUEL LINE FOR THE |
| | TRUCKS? |
| | 6) SHT A5.1 TOILET ROOMS #113 & 122 |
| | SHOWER STALLS SHALL BE ACCESSIBLE. SHOW |
| | BENCH REQUIRED IN STALLS. |
| | 7) SHT A5.1 DRINKING FOUNTAIN SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH 11-4.15 AND ALL SUB- |
| | SECTIONS. ALSO SHOW COMPLIANCE WITH |
| | 11-4.1.3(10)(A) PROVISI0NS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. |
| | 8) SHT P2.2 THE FOLLOWING INFORMATION |
| | WILL BE REQUIRED FOR GAS PERMIT APPLIC- |
| | ATION. (SEPARATE PERMIT REQUIRED) |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 9) SHT P2.3 INDIRECT WASTE FOR ICE MAKER |
| | SHALL BE A FLOOR SINK. FLOOR DRAINS ARE |
| | NOT APPROVED FOR INDIRECT WASTE. 802.3 |
| | 10) SHT P2.3 KITCHEN/DINING ROOM. IN- |
| | DIRECT WASTE REQUIRED FOR ICE MAKER ON |
| | THE COUNTER. SUBMIT A DETAIL. 802.1.1 |
| | 11) PLANS SHALL BE SIGNED. SEALED, AND |
| | DATED BY THE ENGINEER/ARCHITECT OF REC- |
| | ORD. INCLUDE ALL LICENSE NUMBERS ON |
| | TITLE BLOCK AND CERTIFICATE OF AUTHOR- |
| | IZATION IF APPLICABLE. 61G15-23.002/FS |
| | 471.025 - 61G1-16.003-.004/FS481.2055 |
| | 12) OTHER COMMENTS MAY FOLLOW AS THIS |
| | PLAN REVIEW SHOWS THAT PLANS ARE ONLY |
| | 90% COMPLETE. |
| | |