| 2003-11-26 00:00:00 | 1) SITE PLAN DOES NOT REFLECT |
| | EXISTING FIRE HYDRANT LOCATIONS. |
| | |
| | 2) ELECTRONIC SWITCHES WILL BE REQUIRED |
| | ON THE FIRE LINE BACKFLOW DEVICE. |
| | |
| | 3) THE AUTOMATIC GATE ON 50TH STREET |
| | SHALL PROVIDE AT LEAST 20 FEET IN |
| | CLEAR WIDTH. |
| | |
| | 4) PLEASE INDICATE ON PLANS WHICH |
| | OFFICE WILL BE FOR THE FIRE |
| | PREVENTION BUREAU. |
| | |
| | 5) NO FIRE EXTINGUISHER SHOWN |
| | IN COMMUNITY/TRAINING ROOM. |
| | |
| | 6) ROOM NEAR RADIO EQUIPMENT IS |
| | NOT LABELED. |
| | |
| | 7) PROVIDE DETAILS ON FUEL TANK. |
| | PLEASE DISPLAY BARRIER PROTECTION, |
| | WARNING LABELS, AND PROVIDE PRODUCT |
| | APPROVALS. |
| | |
| | 8) ALL NEW STAIRS AND RAMPS SHALL |
| | HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 9) ROOF PLAN DISPLAYS TWO KITCHEN |
| | SUPPLIES AND NO EXHAUST. PLEASE CORRECT. |
| | THE KITCHEN EXHAUST DUCT TERMINATION |
| | SHALL HAVE AT LEAST 10 FEET SEPARATION |
| | FROM KITCHEN SUPPLY. |
| | |
| | 10) THE BUILDING ADDRESS IS REQUIRED |
| | ON THE CORRECT ELEVATION. A MINIMUM |
| | OF AT LEAST 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 11) THE FIRE HYDRANT AND THE FIRE |
| | DEPARTMENT CONNECTION SHALL BE |
| | PROVIDED WITH 7'-6" OF CLEARANCE. |
| | |
| | 12) THE GENERATOR EXHAUST SHALL BE |
| | A MINIMUM OF AT LEAST 10 FEET FROM |
| | ANY BUILDING OPENINGS. |
| | |
| | 13) THE LIGHTING PLAN DOES NOT MATCH |
| | THE LIFE SAFETY PLAN. |
| | |
| | 14) THE FIRE ALARM SYSTEM IS TO BE |
| | UL LISTED FOR CENTRAL STATION SERVICE. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |