| 2003-12-11 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) WHEN THE PLANS ARE SUBMITTED FOR |
| | PERMIT, THE TITLE BLOCK ON EACH SHEET |
| | SHALL INCLUDE THE SIGNATURE, SEAL AND |
| | PRINTED LICENSE NUMBER OF ARCHITECT OR |
| | ENGINEER OF RECORD. |
| | |
| | 2) THE PLANS ARE STATED AS BEING 90% |
| | COMPLETE.THE FOLLOWING REVIEW COMMENTS |
| | ARE BASED ON THE INCOMPLETE PLANS |
| | SUBMITTED. |
| | |
| | 3) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 4) SUBMIT PRODUCT APPROVALS FOR THE |
| | SPANISH 'S' TILE AND FOR THE BUILT UP |
| | ROOFING. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | |
| | 5) SUBMIT PRODUCT APPROVALS FOR THE |
| | WINDOWS, GLASS BLOCK, EXTERIOR DOORS AND |
| | SIDELITES, HURRICANE SHUTTERS AND ROLL- |
| | UP DOORS. |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | |
| | 6) SHEET A6.1THE WINDOW SCHEDULE IS |
| | INCOMPLETE. |
| | |
| | 7) SHEET A2.5THE WALL TYPES PLAN |
| | LEGEND SHOULD BE AMENDED TO REFER TO |
| | SHEET A2.6 FOR THE WALL TYPE DETAILS. |
| | ALSO THE PLAN DOES NOT SHOW A WALL TYPE |
| | FOR MANY OF THE WALLS (JUST SHOWN AS |
| | TYPE X). |
| | |
| | 8) FBC 2405.2SHEET A2.5 SHOWS A NUMBER |
| | OF INTERIOR WALLS WHICH APPEAR TO BE |
| | GLAZED WITHIN 24 INCHES OF DOORS.THESE |
| | ARE'HAZARDOUS LOCATIONS' AND ARE |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 9) FBC 11-4.24.4SHEET A5.3, SECTION 6A |
| | THE PANTRY SINK SHALL BE MAXIMUM 6-1/2" |
| | DEEP.ANNOTATE THE PLANS ACCORDINGLY. |
| | |
| | 10) SHEET A6.4, SECTION 1.WHERE DOES |
| | THIS DETAIL OCCUR?SHOULD IT BE CALLED |
| | UP ON SHEET A4.3, SECTION 2?ANNOTATE |
| | THE PLANS TO SHOW THE LOCATIONS WHERE |
| | THIS DETAIL OCCURS. |
| | |
| | 11) FBC TABLE 1606SHEET S-3, CODES |
| | AND STANDARDS NOTE #1.FOR A FIRE |
| | RESCUE STATION, THE IMPORTANCE FACTOR |
| | SHOULD BE 1.15 (NOT 1.0).AMEND THE |
| | NOTE AND MAKE ANY NECESSARY DESIGN |
| | CHANGES. |
| | |
| | 12) SHEET S-3, WIND LOAD SCHEDULE.THE |
| | ZONE 3 ROOF WIND SUCTION LOAD SHOULD BE |
| | -78.3 PSF (NOT -38.3 PSF).AMEND THE |
| | PLAN. |
| | |
| | 13) SHEET S-4, SECTION 6.THE MONOSLOPE |
| | TRUSSES FOR THE LOWER ROOF ARE SHOWN |
| | SUPPORTED BY LEDGERS BOLTED INTO THE |
| | BOND BEAM.SHEET S-2 (ROOF PLAN) SHOWS |
| | THE TRUSSES TIED DOWN WITH TYPE N |
| | ANCHORS WHICH ARE SIMPSON HHETA 20. THAT |
| | TYPE OF ANCHOR IS NOT SUITABLE FOR |
| | CONNECTION BETWEEN WOOD LEDGERS AND A |
| | WOOD TRUSS SUBJECT TO UPLIFT.AMEND THE |
| | PLAN TO SPECIFY A SUITABLE ANCHOR. |
| | |
| | 14) INFORMATIVE: |
| | SHEET S-3, TRUSS TIE DOWN SCHEDULE.IT |
| | IS NOTED THAT ONLY ANCHOR TYPES B,D & N |
| | ARE SPECIFIED ON THE ROOF PLAN.NOTE |
| | THAT ANCHOR TYPES J & K ARE LISTED AS |
| | 'HUGHES' ANCHORS, AND THAT COMPANY NO |
| | LONGER SUPPLIES TRUSS ANCHORS. |
| | |
| | 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |