| Plan Review Notes For Permit 03110611 |
| Permit Number |
03110611 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-18 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO | | | THE PLAN FOR CODE COMPLIANCE AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LIST THE DRYER IN THE LOAD | | | CALCS AND ON PANEL SCHEDULE PER | | | 220.18(5KW). | | | | | | 2} PLEASE NOTE THAT THE ADDITIONAL | | | LIGHTING LOAD LISTED ON THE PANEL IS # | | | 14 ON A 20 AMP BREAKER,SEE 310.16.ALSO | | | RECALCULATE THE NUMBER OF NEW CIRCUITS | | | AS IT WILL BE MORE THAN ONE. | | | | | | 3} PLEASE SEE 220.16(B) FOR LAUNDRY | | | LOAD. | | | | | | 4} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210.11(C)(3). | | | MUST BE 20A AND #12AWG. | | | | | | 5} THE FAMILY ROOM IS LISTED AS | | | NEW.PLEASE SHOW ALL NEW WIRING FOR NEW | | | ROOMS. | | | | | | 6} PLEASE NOTE THAT SMOKE DETECTORS MUST | | | BE ADDED TO COMPLY WITH 8-1.4.1.6 NFPA- | | | 72. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|