2003-11-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO
 THE PLAN FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} PLEASE LIST THE DRYER IN THE LOAD
 CALCS AND ON PANEL SCHEDULE PER
 220.18(5KW).
  
 2} PLEASE NOTE THAT THE ADDITIONAL
 LIGHTING LOAD LISTED ON THE PANEL IS #
 14 ON A 20 AMP BREAKER,SEE 310.16.ALSO
 RECALCULATE THE NUMBER OF NEW CIRCUITS
 AS IT WILL BE MORE THAN ONE.
  
 3} PLEASE SEE 220.16(B) FOR LAUNDRY
 LOAD.
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210.11(C)(3).
 MUST BE 20A AND #12AWG.
  
 5} THE FAMILY ROOM IS LISTED AS
 NEW.PLEASE SHOW ALL NEW WIRING FOR NEW
 ROOMS.
  
 6} PLEASE NOTE THAT SMOKE DETECTORS MUST
 BE ADDED TO COMPLY WITH 8-1.4.1.6 NFPA-
 72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.