Text |
| 2004-11-30 00:00:00 | *********** UNSAT ******** |
| | |
| | 1)NOTE: PLEASE SEE # OF CONDUCTORS |
| | INDICATED ON RISER FROM METER TO MAIN. |
| | THIS IS A 3-PHASE SERVICE, YET ONLY |
| | SHOWS 3-CONDUCTORS. |
| | |
| | 2)NOTE: PLEASE ALSO SEE #OF CONDUCTORS |
| | SHOWN IN A SINGLE 2" CONDUIT. PLEASE |
| | SEE |
| | TABLES IN CHAPTER 9 NEC FOR CONDUIT |
| | FILL. |
| | |
| | 3)NOTE: PLEASE SEE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS NOW SHOWN FROM |
| | METER TO MAIN. AN EQUIPMENT GRND IS NOT |
| | INSTALLED FROM METER TO THE FIRST MEANS |
| | OF DISCONNECT. 250.6,250.24. |
| | |
| | 4)NOTE: PLEASE CORRELATE RISER WITH |
| | PANEL "A" FEEDER SCHEDULE, AS ON NOTES |
| | ABOVE. |
| | |
| | 5)NOTE: PLEASE SEE RE-SUB SHEET |
| | MENTIONS |
| | PERMIT APPLIACTION TO BE BROUGHT IN BY |
| | THE 11/24. THIS IS REQUIRED WHEN |
| | RE-SUBMITTING PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEET(S) FOR COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | |
| | PLEASE BE SURE ALL REVIEWS ARE DONE |
| | BEFORE MAKING ANY CORRECTIONS, DUE TO |
| | ANY POSSIBLE COMMENTS FROM OTHER |
| | REVIEW(ERS). |
| | |