| 2004-12-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | IGNORE COMMENT #2 BELOW.ARCHITECT OF |
| | RECORD REDLINED, SIGNED AND DATED A |
| | HANDWRITTEN NOTE, GIVING WINDOW TYPE |
| | AND SIZE. THE OTHER COMMENTS STILL |
| | APPLY |
| | |
| | |
| 2004-12-10 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | THE MARION CONSTRUCTION COMMENT RESPONSE |
| | LETTER DATED 11/22/04 IS NOTED WITH THE |
| | FOLLOWING COMMENTS: |
| | |
| | 1) THE DOORS AND WINDOWS IN THE NEW |
| | METAL BUILDING ARE STATED TO BE PART OF |
| | THE METAL BUILDING DESIGN SUBMITTAL |
| | PACKAGE BUT AS OF 12/10/04 THAT PACKAGE |
| | HAS NOT BEEN SUBMITTEDTO THIS OFFICE. |
| | THE DOOR AND WINDOW PRODUCT APPROVALS |
| | ARE REQUIRED BEFORE THE PERMIT CAM BE |
| | ISSUED. |
| | |
| | 2) SUBMITTAL OF A PRODUCT APPROVAL FOR |
| | PGT SINGLE HUNG WINDOWS IS NOTED, BUT |
| | THE PLANS DO NOT STATE THE SIZE OR TYPE |
| | OF WINDOWS SO THAT THE DESIGN WIND |
| | PRESSURES GIVEN IN THE PRODUCT APPROVAL |
| | MAY BE VERIFIED. |
| | |
| | --PROVISO-- |
| | A SEPARATE PERMIT APPLICATION AND |
| | PRODUCT APPROVAL PACKAGE WILL BE |
| | REQUIRED FOR THE BUILT-UP ROOFING. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |