| 2004-10-15 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | THIS IS REQUIRED AT THIS TIME. |
| | |
| | 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/EXT LTS. |
| | |
| | 3)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MCB TO PANEL |
| | "B".? 250.110,250.24,250.122 |
| | |
| | 4)NOTE: PLEASE SEE PANEL "B" IS SHOWN ON |
| | A SP BRKR SPACE? #29 PLEASE SEE FEED TO |
| | PANEL "B" IS SHOWN AS A 3P-200A BRKR TO |
| | PANEL "B" WHICH IS INDICATED AS A SINGLE |
| | PHASE PANEL ON PANEL SCHEDULE INFORMAT- |
| | -ION?? WHICH ONE? |
| | |
| | 5)NOTE: PLEASE SEE SPACE #28 ON PANEL |
| | SCHEDULE "A". THIS SHOWS AN ADDITIONAL |
| | 2-P60A BRKR FOR SUB PANEL "B". |
| | PLEASE CLARIFY?? |
| | IF THERE IS INDEED AN ADDITIONAL 60A |
| | SUB-PANEL, PLEASE ALSO INCLUDE THIS ON |
| | RISER DIAGRAM. |
| | |
| | 6 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE SEE PLAN S DO NOT INLCUDE ANY |
| | LOAD CALCULATIONS? |
| | PLEASE SEE 220.3 FOR SPECIFIC LIGHTING |
| | LOADS FOR HIGH-BAY FIXTURES ETC. |
| | |
| | 7)NOTE: PLEASE SEE 600.5 FOR REQUIRED |
| | SIGN CIRCUIT. EXISTING OR NEW?? |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |