Plan Review Notes For Permit 03110607
Permit Number 03110607
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SANT. RISER DIAGRAM. SERVICE
 SINK AND DRINKING FOUNTAIN SHALL NOT
 DRAIN THROUGH THE WET VENT FOR THE BATH
 ROOM FIXTURES. 909.1 - THE SERVICE SINK
 AND DRINKING FOUNTAIN SHALL CONNECT
 DOWNSTREAM OF THE BATHROOM FIXTURES.
 2) PROVISIONS SHALL BE MADE FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING
 SECTION 11-4.1.3(10)(A). (A DRINKING CUP
 DISPENSER WILL MEET THIS REQUIREMENT)
 3) SUBMIT A DETAIL SHOWINC COMPLIANCE
 WITH 11-4.24 FOR THE LOUNGE SINK.
  
 REVIEW BY KEN STEVENS