| 2003-11-26 00:00:00 | 1) BUILDING ADDRESS REQUIRED. 6" HIGH |
| | NUMBERS ARE REQUIRED. |
| | |
| | 2) 10" TREADS ARE NOT PERMITTED ON |
| | STAIRS. EXIT STAIRS FROM SECOND FLOOR |
| | THAT LEADS TO THE EXTERIOR DISPLAYS |
| | 10" TREADS. |
| | |
| | 3) HOW DOES FIRE AND PARAMEDICAL |
| | EQUIPMENT GAIN ACCESS THRU NEW GATE. |
| | |
| | 4) DEMOLITION ACTIVITIES TO COMPLY |
| | WITH NFPA 241, THE STANDARD FOR |
| | DEMOLITION, RENOVATION, AND CONSTRUCTION |
| | |
| | 5) SITE PLAN DOES NOT INDICATE ANY |
| | EXISTING OR NEW FIRE HYDRANTS FOR THE |
| | VICINITY. |
| | |
| | 6) PLEASE PROVIDE HEIGHTS OF THE |
| | PROPOSED STORAGE RACKS. |
| | |
| | 7) THE 42" AISLE NEAR THE DISPATCH |
| | AREA SHALL BE AT LEAST 44" WIDE. |
| | |
| | 8) WHAT IS PLANNED TO BE STORED ON |
| | THE STORAGE RACKS. |
| | |
| | 9) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND |
| | CEILINGS. |
| | |
| | 10) THE 2668 DOOR FOR THE STORAGE ROOM |
| | UNDER THE STAIRS SHALL BE AT LEAST |
| | 45 MINUTE FIRE RATED. |
| | |
| | 11) NO INDICATION THAT THE STORAGE |
| | ROOM OR STAIR DOOR ARE RATED AT THE |
| | SECOND FLOOR/MEZZANINE PLAN. |
| | |
| | 12) TACTILE SIGNAGE REQUIRED AT STAIRS. |
| | |
| | 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GAURDRAILS. |
| | |
| | 14) ARE ANY EMERGENCY LIGHTS PRESENT |
| | IN THE STAIRS. ALSO ARE ALL EXIT |
| | SIGNS SHOWN ON E-1. NO EMERGENCY |
| | LIGHTING IN WAREHOUSE. |
| | |
| | 15) WELDER NOTED ON PAGE E-3. ALL |
| | WELDING MUST BE APPROVED BY THE |
| | BUREAU OF FIRE PREVENTION. ALL |
| | WELDING OPERATIONS TO COMPLY WITH |
| | NFPA 51B. A CLEAR RADIUS OF 35 FEET |
| | IS REQUIRED FROM WELDING TO COMBUSTIBLES |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |