| Plan Review Notes For Permit 03110570 |
| Permit Number |
03110570 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-10 00:00:00 | PROVISO: | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED ON SYSTEMS THAT HAVE THE DESIGN | | | CAPACITY OR COMBINED SYSTEMS GREATER | | | THAN 2,000 CFM.SHUTDOWN SHALL HAVE | | | NOTIFICATION TO ALARM/STROBE IN NORMALLY | | | OCCUPIED AREAS. | | | 2001 FBC(M) 606.2.1, 606.4 & NFPA 90A | | | 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|