| Date |
Text |
| 2003-12-23 00:00:00 | DENIED |
| | |
| | 1) 1001.1.3/ 1005.4 ZERO LOT LINE |
| | EGRESS:WHEN ACCESS TO OR FROM A RE- |
| | QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| | ING OF A STRUCTURE TO THE PUBLIC WAY, |
| | REQUIRES TRANSVERSING A PROPERTY |
| | (ADJOINING LOT) THAT IS NOT PART OF THE |
| | ONE WHICH THE STRUCTURE IS LOCATED, AN |
| | EGRESS EASEMENT THROUGH THE ADJOINING |
| | PROPERTY IS REQUIRED AND SHALL BE RECORD |
| | ED IN THE COUNTY RECORDS. THIS EASEMENT |
| | SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| | ING SHALL BE PLACED WITHIN THE EASEMENT |
| | AREA WHICH WOULD BLOCK ACCESS TO THE |
| | EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| | FROM THE RESCUE OPENING TO THE PUBLIC |
| | WAY. NO LANDSCAPING, FENCES OR OTHER |
| | IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| | EASEMENT. |
| | THE COVENANTS FOR VILLAGIO THAT WAS |
| | SUBMITTED DOES NOT COMPLY WITH THE |
| | REQUIREMENTS FOR AN EGRESS EASEMENT. |
| | SUBMIT A REVISED AND RECORDED AMENDMENT |
| | TO THE COVENANTS THAT MEETS THE ABOVE |
| | REQUIREMENTS. |
| | |
| | 2) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT A CITY OF WPB |
| | APPLICATION FORM FOR LOCAL PRODUCT |
| | APPROVAL PER FAC RULE 9B-72. SEE |
| | FORM ATTACHED. |
| | |
| | 3) SAFEGUARD STORM PANELS ARE NO LONGER |
| | IN BUSINESS AND DO NOT HAVE A CURRENT |
| | NOA. SUBMIT THE REQUIRED STORM PANEL |
| | INFORMATION FROM A COMPANY WITH STATE OR |
| | LOCAL PRODUCT APPROVAL. |
| | |
| | 4) THE 36SH WINDOW IN THE DEN EXCEEDS |
| | THE 20% WALL AREA ALLOWED AS OPENING BY |
| | FBC TABLE 600. REVISE TO A 26SH OR |
| | SMALLER WINDOW THAT MEETS EGRESS |
| | REQUIREMENTS. |
| | |
| | 5) THE BUILDING CATEGORY IS INCORRECTLY |
| | GIVEN AS R3 ON SHEET 6. THE BUILDING |
| | CATEGORY IS II, R3 IS THE OCCUPANCY |
| | CLASSIFICATION. PLEASE CORRECT. |
| | |
| | 6) THE TOP AND BOTTOM CHORD DEAD LOADS |
| | ARE NOT INDICATED ON SHEET 6. PLEASE |
| | LIST THE BOTTOM CORD LIVE LOAD AS WELL. |
| | THE BOTTOM CORD L.L. IS 10 PSF WITHOUT |
| | ATTIC STORAGE AND 30 PSF WITH ATTIC |
| | STORAGE PER FBC TABLE 1604.1. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |