| Plan Review Notes For Permit 03110555 |
| Permit Number |
03110555 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-10 00:00:00 | DENIED: | | | RETURN AIR JUMPER FROM THE MASTER | | | BEDROOM IS NOT SIZED PROPERLY.PER THE | | | REVISION TO THE 2001 FBC(M) 601.4 | | | EFFECTIVE JUNE 30, 2003, ALL SUPPLY AIR | | | INTO THE MASTER SUITE (BATHROOM, | | | CLOSET, ETC) IS TO BE INCLUDED IN THE | | | CALCULATION FOR A "TOTAL" OF SUPPLY AIR | | | TO THAT AREA.SEE THE ATTACHED | | | SCHEDULE FOR PROPER SIZING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|