| Plan Review Notes For Permit 03110552 |
| Permit Number |
03110552 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-02-20 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW PRIOR TO FINAL INSPECTION. | | | | | | 1} ITEM #2 FROM LAST REVIEW WAS NOT | | | ADDRESSED. SUBMIT A PANEL SCHEDULE | | | INDICATING WIRE AND OCP SIZES. | | | | | | 2} ITEMS #4 & 5 FROM LAST REVIEW ARE | | | REDLINED ON THIS PLAN FOR COMPLIANCE, | | | SHOW ACTUAL LOCATION ON RESUBMITTED | | | PLANS. | | | | | | 3} SHOW LOCATION OF THE PANEL ON THE 2ND | | | FLOOR. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|