| Date |
Text |
| 2004-01-30 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} REGARDING THE PANEL RELOCATION |
| | SUBMITTHE FOLLOWING: |
| | A) A RISER DIAGRAM OF RELOCATED |
| | EQUIPMENT. |
| | B) DISCONNECTING MEANS FOR THE CIRCUITS |
| | REFEEDING THE HOUSE PER 225.31. |
| | C) GROUNDING PER 250.32. |
| | D) AIC FOR EQUIPMENT PER 110.9 & 110.10 |
| | EVEN IF REUSING THE SAME EQUIPMENT |
| | THE AIC CALC WILL CHANGE DEPENDING |
| | ON THE LENGTH OF WIRE FROM THE |
| | TRANSFORMER LOCATION. |
| | |
| | 2} A PANEL SCHEDULE INDICATING WIRE AND |
| | OCP SIZES SO AS TO DETERMINE COMPLIANCE |
| | WITH CODE ARTICLES IG: 210.11(C)(1),(2) |
| | & (3). 210.12 ETC. |
| | |
| | 3} A LOAD CALCULATION PER 215.5. |
| | |
| | 4} INDICATE COMPLIANCE WITH 210.63 IF |
| | APPLICABLE. |
| | |
| | 5} INDICATE COMPLIANCE WITH 210.52(E). |
| | |
| | 6} THERE MAY BE ADDITIONAL COMMENTS WHEN |
| | THE PLANS ARE RESUBMITTED FROM THE |
| | ARCHITECT. |
| | |
| | 7} PLEASE NOTE THAT TWO SETS OF PLANS |
| | ARE REQUIRED TO BE SUBMITTED FOR REVIEW |
| | PER 104 FBC. |
| | |
| | 8} ALL PLANS CONTAINING AN ARCHITECTS |
| | SEAL ARE REQUIRED TO BE PREPARED BY HIM. |
| | PLEASE ALSO INCLUDE CERTIFICATE OF |
| | AUTHORIZATION NUMBERS WHERE REQUIRED. |
| | ALSO A TITLE BLOCK IS REQUIRED.SEE |
| | FS 481.219, FAC 61G1-16.004 FOR ABOVE |
| | STATED REQUIREMENTS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |