| Plan Review Notes For Permit 03110495 |
| Permit Number |
03110495 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-01-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A3 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. | | | A) W/C AND TUB ARE NOT VENTED IN BATH | | | #1 901.2.1 | | | B) LAV MISSING IN BATH #2 | | | C) KITCHEN IS ON SAME END OF HOUSE AS | | | THE WASH MACHINE. | | | D) TWO LAVS IN BATH #1 (LABELED SINKS). | | | E) SIZE REQUIRED ON ALL PIPE SECTIONS. | | | F) CLEANOUT REQUIRED ABOVE WASH MACHINE | | | AND A STANDPIPE IS REQUIRED. 406.3 AND | | | 708.10 | | | 2) SEE EXAMPLE OF A SANITARY RISER DIA- | | | GRAM THAT MEETS CODE REQUIREMENTS AND | | | REFLECTS THE FLOOR PLAN. TO EXPEDITE | | | YOUR PLANS IN THE FUTURE, I SUGGEST THAT | | | YOUR PLUMBING CONTRACTOR LAYOUT THE | | | RISER AS IT WILL BE INSTALLED AS AN EX- | | | AMPLE OF A RISER DIAGRAM THAT WILL MEET | | | CODE AND REFLECT THE FLOOR PLAN. | | | SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|