Plan Review Notes
Plan Review Notes For Permit 03110495
Permit Number 03110495
Review Stop P
Sequence Number 2
Notes
Date Text
2004-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A3 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) W/C AND TUB ARE NOT VENTED IN BATH
 #1 901.2.1
 B) LAV MISSING IN BATH #2
 C) KITCHEN IS ON SAME END OF HOUSE AS
 THE WASH MACHINE.
 D) TWO LAVS IN BATH #1 (LABELED SINKS).
 E) SIZE REQUIRED ON ALL PIPE SECTIONS.
 F) CLEANOUT REQUIRED ABOVE WASH MACHINE
 AND A STANDPIPE IS REQUIRED. 406.3 AND
 708.10
 2) SEE EXAMPLE OF A SANITARY RISER DIA-
 GRAM THAT MEETS CODE REQUIREMENTS AND
 REFLECTS THE FLOOR PLAN. TO EXPEDITE
 YOUR PLANS IN THE FUTURE, I SUGGEST THAT
 YOUR PLUMBING CONTRACTOR LAYOUT THE
 RISER AS IT WILL BE INSTALLED AS AN EX-
 AMPLE OF A RISER DIAGRAM THAT WILL MEET
 CODE AND REFLECT THE FLOOR PLAN.
 SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]