| Plan Review Notes For Permit 03110495 |
| Permit Number |
03110495 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-26 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING REVISIONS FOR | | | CODE COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 3} PLEASE NOTE KITCHEN COUNTER- | | | -SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5. | | | | | | 4} PLEASE CLARIFY THE NOTE SHOWING | | | OVERHEAD ELECTRIC BETWEEN THE METER AND | | | THE DISCONNECT. | | | | | | 5}THERE ARE SMOKE DETECTORS MISSING | | | OUTSIDE TWO BEDROOMS PER 8-1.4.1.6.(2). | | | | | | SEE A/C COMPRESSER ON PANEL SCHED @ | | | 1200 WATTS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|