Plan Review Notes
Plan Review Notes For Permit 03110495
Permit Number 03110495
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-26 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING REVISIONS FOR
 CODE COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 4} PLEASE CLARIFY THE NOTE SHOWING
 OVERHEAD ELECTRIC BETWEEN THE METER AND
 THE DISCONNECT.
  
 5}THERE ARE SMOKE DETECTORS MISSING
 OUTSIDE TWO BEDROOMS PER 8-1.4.1.6.(2).
  
 SEE A/C COMPRESSER ON PANEL SCHED @
 1200 WATTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718