2004-01-06 00:00:00BUILDING REVIEW CHECKLIST:
 1-SURVEY FOOTPRINT DOESN'T MATCH PLANS.
 2-AFFINITI ARCHITECT TO SIGN, SEAL,DATE
 ALL PLANS AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTES WHEN SUBMITTING PLANS
 FOR PUBLIC RECORDS. ALSO, SEE REQ'D
 INFORMATION TO BE ON TITLE BLOCK.
 3-PERMIT ENGINEERING SERVICES COMPANY
 REGISTERED NUMBER DOESN'T MATCH NUMBER
 ON FBPE. CLARIFY/REVISE AS REQ'D.
 4-DESIGN CRITERIA: NEED TO ADD 30PSF OR
 10PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 6-CLARIFY IF FIXED WINDOWS AT DINING,
 LIVING ROOM AND ALL TRANSOM WINDOWS
 ARE BUTT GLAZING, STRUCTURAL MULLIONS
 OR FIXED MUNTINGS. REVISE DWGS TO
 SHOW CORRECT INSTALLATION. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-IMPACT GLAZING AT DEN WINDOW WILL NOT
 COMPLY WITH SECTION 1005.4.5. NEED TO
 PROVIDE EMERGENCY EGRESS FROM AN AREA
 THAT CANN'T BE LOCKED. REVISE STORM
 SHUTTERS INSTALLATION SCHEDULE AS WELL
 8-PROVIDE FLORIDA PRODUCT APPROVAL OR
 COMPLETE SITE SPECIFIC ENGINEERING W/
 ALL DOCUMENTATION REQUIRED BY THE
 STATE (SEE WWW.FLORIDABUILDING.ORG)
 FOR ROYAL WALL SYSTEM, SLIDING GLASS
 DOORS, SINGLE HUNG WINDOWS,ENTRY DOOR,
 GARAGE DOORS, TRUSS ANCHORS,ROOF TILE,
 FIXED WINDOWS, WINDOW MULLIONS, GLASS
 BLOCK.
 9-PROVIDE FLORIDA PRODUCT APPROVAL OR
 SITE SPECIFIC COMPLETE INFORMATION FOR
 STORM SHUTTERS. KEY PLAN TO MATCH
 PLANS, INSTALLATION SCHEDULE TO MATCH
 INFORMATION ON ENGINEERED DWGS. THIS
 MODEL HAS WOOD APPLICATIONS ALSO.
 10-PROVIDE COMPLETE GABLE END DETAIL
 SHOWING COMPLIANCE WITH SEC. 2117 FBC
 WHICH REQUIRES STRUCTURAL CONTINUITY.
 11-CLARIFY WHY ARE THERE TWO DIFFERENT
 TRUSS ANCHOR SCHEDULES. SEE SHEET RF-1
 AND SD-2. ALSO, UPDATE TRUSS ANCHOR
 SCHEDULE AND ALL DETAILS THAT ARE
 AFFECTED BY SEC. 1609.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE STEEL STRESS
 TO BE INCREASED.
 **NOTE: ONLY USP 2003 AND SIMPSON HIGH
 WIND RESISTANT CONSTRUCTION CATALOGUES
 WERE REVISED TO SATISFY THIS SECTION.
 USE IETHER WHEN SELECTING CONNECTORS.
 PROVIDE COMPLETE ENGINEERING ANALYSIS
 FOR DIFFERENT VALUES AND FASTENINGS
 OTHER THAN THOSE PUBLISHED.
 12-NEED RECORDED NOTICE OF COMMENCEMENT.
 13-OWES $18.20 FOR UPDATED VALUATION.
 14-SHEET #3: A)UPDATE CONNECTORS. HUGHES
 IS OUT OF BUSINESS. SEE COMMENTS.
 B)REVISE HANDRAIL HEIGHT SHOWN ON BLDG
 SECTION 1/3. SEE SEC. 1007.5.1 FBC/01.
 C)STUCCO TO BE 7/8" MIN. SEE ASTM C-926.
 D)PROVIDE GIRDER/WALL CONNECTION DETAIL
 THAT REFLECTS ACTUAL CONDITIONS SHOWN
 ON PLANS. SAME APPLIES TO 2 STORY
 BEARING WALL. DON'T USE GENERIC DETAIL
 15-SHEET #7: A) CLARIFY/UPDATE INFO.
 SEE COMMENTS.
 16-SHEET #1 OF STRUCTURAL DRAWINGS:
 A)PROVIDE DETAIL/SPECS FOR CONNECTION
 OF ROYAL WALL SYSTEM TO WOOD FRAMING.
 IT SAYS CONNECTION BY BUILDER, BUT,
 THERE ARE NOT SPECS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)PROVIDE COMPLETE DETAILS/SPECS FOR
 FRAMED WALL BY OTHERS. NEED COMPLETE
 DETAILS/SPECS, CONNECTIONS, FRAMING
 FOR OPENINGS TO RECEIVE STORM SHUTTERS
 & SHOW HOW SHEARWALL ARE TRANSFERRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.