Plan Review Notes
Plan Review Notes For Permit 03110439
Permit Number 03110439
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-14 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION
 SHOWING EXISTING LOADS AND ALL NEW
 LOADS.SEE ARTICLE 220 NEC.THE
 CALCULATION GIVEN IS NOT IN THE CORRECT
 FORMAT.
 ALSO THE NOTE INDICATING A/C WILL NOT
 BE USED WHEN HEATER IS IN USE IS NOT
 ACCEPTABLE,THERE IS NO LANGUAGE IN THE
 NEC THAT CONSIDERS THESE NON-CONCURRENT
 LOADS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.