| Plan Review Notes For Permit 03110439 |
| Permit Number |
03110439 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-14 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE A LOAD CALCULATION | | | SHOWING EXISTING LOADS AND ALL NEW | | | LOADS.SEE ARTICLE 220 NEC.THE | | | CALCULATION GIVEN IS NOT IN THE CORRECT | | | FORMAT. | | | ALSO THE NOTE INDICATING A/C WILL NOT | | | BE USED WHEN HEATER IS IN USE IS NOT | | | ACCEPTABLE,THERE IS NO LANGUAGE IN THE | | | NEC THAT CONSIDERS THESE NON-CONCURRENT | | | LOADS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|