| Plan Review Notes For Permit 03110341 |
| Permit Number |
03110341 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-14 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE SUBMIT PLANS THAT SHOW THE | | | ENTIRE SCOPE OF WORK,INCLUDING ALL | | | INTERIOR WIRING.INCREASE THE VALUE OF | | | THE PROJECT TO REFLECT ALL WORK,LABOR | | | AND MATERIAL.PLANS MUST COMPLY WITH 104. | | | 2 & 104.2.1.3 SPECIFICALLY,SEE ATTACHED | | | COPY OF FBC. | | | | | | THE ENGINEER DID NOT SEAL THE PLANS AND | | | HIS TITLE BLOCK IS INCORRECT. SEE CH 471 | | | FS AND 61G15-23.002 FAC. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110.9. | | | | | | 2}SHOW THE SERVICE LOCATION ON THE PLAN. | | | | | | 3} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 210.12 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|