Plan Review Notes
Plan Review Notes For Permit 03110341
Permit Number 03110341
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-14 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SUBMIT PLANS THAT SHOW THE
 ENTIRE SCOPE OF WORK,INCLUDING ALL
 INTERIOR WIRING.INCREASE THE VALUE OF
 THE PROJECT TO REFLECT ALL WORK,LABOR
 AND MATERIAL.PLANS MUST COMPLY WITH 104.
 2 & 104.2.1.3 SPECIFICALLY,SEE ATTACHED
 COPY OF FBC.
  
 THE ENGINEER DID NOT SEAL THE PLANS AND
 HIS TITLE BLOCK IS INCORRECT. SEE CH 471
 FS AND 61G15-23.002 FAC.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 2}SHOW THE SERVICE LOCATION ON THE PLAN.
  
 3} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210.12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718