Plan Review Notes
Plan Review Notes For Permit 03110330
Permit Number 03110330
Review Stop M
Sequence Number 2
Notes
Date Text
2003-12-30 00:00:00DENIED:
 PROVISO FROM PREVIOUS REVIEW BY HAROLD
 MOSER WAS NOT ADDRESSED.
 RETURN AIR REQUIRED FROM BEDROOM AREAS
 PER REVISION TO THE 2001 FBC(M) 601.4.
 PLEASE PROVIDE PLANS INDICATING RETURN
 OR TRANSFER AIR DUCT/GRILLES.INDICATE
 DUCT/GRILLE SIZES SHOWING COMPLIANCE
 WITH THE AFOREMENTIONED CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.