| Notes |
| Date |
Text |
| 2004-03-19 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW WITH NEXT REVISION OR ON AS-BUILT | | | DRAWING. | | | | | | 1} THE OCP AND WIRE SIZE FOR THE SUB | | | PANEL FEED IS INCORRECTLY LISTED ON | | | PANEL SCHEDULE "A". | | | | | | 2} SHOW COMPLIANCE WITH 250.122 FOR SUB | | | PANEL FEEDER. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|