| Notes |
| Date |
Text |
| 2003-12-29 00:00:00 | *****PROVISO***** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE ENGINEER'S NAME AND LICENSE | | | NUMBER IS TO BE PRINTED ON THE PLAN | | | FAC61G15-23.002.REVISE SHEETS | | | 1,3,4,6,RF1, 1,SD1,SD2. | | | | | | 2.)HHGT1 AND HHGT2, CONNECTOR KST260, | | | NAILING CONFLICTS WITH CATALOG AND | | | DESIGN UPLIFT ON PLAN EXCEEDS MAX | | | ALLOWED BY THE CATALOG.REVISE RF1. | | | | | | 3.)WOOD TO WOOD CONNECTORS ARE | | | USED IN WOOD TO MASONRY APPLICATION; | | | ADDRESS.REVISE RF1 OR SUBMIT | | | CALCULATIONS. | | | | | | 4.)SUBMIT SITE SPECIFIC OR STATEWIDE | | | PRODUCT APPROVAL FOR THE FOLLOWING: | | | GARAGE DOOR | | | GLASS BLOCK | | | SHUTTERS | | | FIXED GLASS | | | | | | ******SUBMIT REVISIONS BEFORE FRAMING | | | INSPECTION******** |
|