Plan Review Notes
Plan Review Notes For Permit 03110111
Permit Number 03110111
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-04 00:00:00*****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE ENGINEER'S NAME AND LICENSE
 NUMBER IS TO BE PRINTED ON THE PLAN,
 FAC61G15-23.002.
  
 2.)THE GIRDER/WALL CONNECTION (SHEET
 3) SPECIFIES HUGHES CONNECTORS; HUGHES
 IS NO LONGER IN BUSINESS.
  
 3.)THE WOOD CONSTRUCTION NOTES, ITEM
 #4, REFERS TO FBC3218.17.NOT IN THE
 FBC CODE BOOK.
  
 4.)HHGT1 AND HHGT2, CONNECTOR KST260
 SHEET RF1, NAILING CONFLICTS WITH
 CATALOG AND DESIGN UPLIFT ON THE PLAN
 EXCEEDS MAX ALLOWED BY THE CATALOG
 (USE THE GREY BAR WITHOUT STRESS
 INCREASE FOR STEEL, USP2003 CATALOG).
  
 5.)WOOD-TO-WOOD CONNECTORS ARE
 SPECIFIED IN WOOD-TO MASONRY
 APPLICATIONS; FOR EXAMPLE, USP HTW.
 ADDRESS (SHEET RF1).CHECK ALL
 CONNECTORS.
  
 6.)PROVIDE A FIREBLOCK DETAIL FOR THE
 DROPPED CEILINGS/SOFFITS, FBC705.3,
 2305.1.4.
  
 7.)STATEWIDE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 GARAGE DOOR
 GLASS BLOCK
 SHUTTERS
 TRUSS CONNECTORS
 FIXED GLASS
 FIXED GLASS IMPACT
 FOR THE ABOVE ITEMS, PROVIDE COVER SHEET
 OF THE STATEWIDE PRODUCT APPROVAL, IF
 AVAILABLE, WITH THE NOA OR SBCCI REPORT.
 PRODUCT APPROVAL ALSO REQUIRED FOR
 CONNECTORS.PROVIDE A SCHEDULE OF
 CONNECTORS WITH THE STATE APPROVAL
 NUMBER LISTED.
  
 FOR MORE INFORMATION,
 WWW.FLORIDABUILDING.ORG.
  
 8.)THE ARCHITECTURALS ARE FOR A
 GARAGE LEFT, SITE PLAN AND STRUCTURALS
 FOR GARAGE RIGHT.
  
 9.)ADDITIONAL FEES DUE, RADON, SEE
 ATTACHED BZ231386.
  
 10.) AFFINITI ARCHITECTS SHOULD NOT BE
 ON THE PLAN IF THE PLAN IS SEALED BY
 ANOTHER ARCHITECT.REMOVE AFFINITI'S
 TITLE BLOCK FROM THE PLAN.
  
 11.)SAFEGUARD (STORM SHUTTER SBCCI
 REPORT) IS NO LONGER IN BUSINESS. SUBMIT
 VALID PRODUCT APPROVALS FOR STORM
 SHUTTERS.