| Plan Review Notes For Permit 03110107 |
| Permit Number |
03110107 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-19 00:00:00 | | | | BUILDINGCOMMENTS | | | ---------------- | | | | | | PERMIT APPLICATION SHALL BE TRANSFERED | | | TO A LICENSED STRUCTURAL CONTRACTOR. | | | | | | PROVIDE COMPLETE DETAILS FOR STAIR CON | | | STRUCTION. DETAIL CONNECTION OF DECK TO | | | EXISTING STRUCTURE. | | | | | | SUBMIT GUARDRAIL AND PICKET SPEC'S. | | | | | | IDENTIFY ALL HARDWARE AND FASTENERS. | | | | | | EXTERIOR STAIRS SHALL BE MIN. 10' FROM | | | ALL BUILDINGS AND P/L'S. | | | | | | | | | | | | | | | L. MARTINEZ | | | 805-6710 |
|