| Plan Review Notes For Permit 03110106 |
| Permit Number |
03110106 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-13 00:00:00 | ****CORRECTIONS**** | | | PROVISO SUBMITTALS | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SHEET M1 HAS BEEN REVIEWED FOR | | | CODE COMPLIANCE AND STAMPED.ALSO | | | REVIEWED WERE THE PRODUCT APPROVALS FOR | | | GLASS BLOCK,FIXED WINDOW, GARAGE DOORS. | | | | | | 2.)IT IS UNCLEAR AS TO WHAT CHANGES | | | WERE MADE ON THE ARCHITECTURALS. CHANGES | | | ARE TO BE DATED AND CLEARLY INDICATED. | | | | | | 3.)THE CONNECTORS WHICH HAVE BEEN | | | APPROVED FOR USE IN A WOOD-TO-WOOD | | | APPLICATION CANNOT BE USED IN A WOOD-TO- | | | CONCRETE OR WOOD-TO-STEEL APPLICATION. | | | CONNECTORS CAN BE ENGINEERED.REVISE | | | STRUCTURAL SHEETS AS NECESSARY. | | | | | | 4.)SEPARATE PERMIT FOR SHUTTERS. | | | | | | 5.)SITE SPECIFIC PRODUCT APPROVAL | | | WAS SUBMITTED FOR THE ROYALL WALL.THE | | | PAPERWORK IS NOT IN COMPLIANCE WITH | | | RULE 9B-72.SEE ATTACHED POLICY IN | | | REGARDS TO ROYALL WALL. | | | | | | 6.)REVISIONS SHOULD BE SUBMITTED AS | | | SUCH, NOT AS SUBMITTALS.ADDITIONAL | | | FEES DUE. | | | | | | 7.)SEPARATE PERMIT FOR SHUTTERS. | | | | | | 8.)SUBMIT STATEWIDE, LOCAL OR SITE | | | SPECIFIC PRODUCT APPROVAL FOR THE | | | OUTSWING GLAZED DOORS. |
|