Plan Review Notes
Plan Review Notes For Permit 03110106
Permit Number 03110106
Review Stop B
Sequence Number 2
Notes
Date Text
2003-12-30 00:00:00****PROVISO*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HHGT1 AND HHGT2, CONNECTOR KST260,
 NAILING CONFLICTS WITH CATALOG AND
 DESIGN UPLIFT ON PLAN EXCEEDS MAX
 ALLOWED BY THE CATALOG.REVISE RF1.
  
 2.)WOOD TO WOOD CONNECTORS ARE USED
 IN WOOD TO MASONRY APPLICATION; ADDRESS.
 REVISE RF1 OR SUBMIT CALCULATIONS.
  
 3.)SUBMIT SITE SPECIFIC OR STATEWIDE
 PRODUCT APPROVALS FOR THE FOLLOWING:
 GARAGE DOOR
 GLASS BLOCK
 SHUTTERS
 FIXED GLASS
  
 *****SUBMIT REVISIONS BEFORE FRAMING
 INSPECTION******