Plan Review Notes
Plan Review Notes For Permit 03110106
Permit Number 03110106
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-08 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE ENGINEER'S NAME AND LICENSE
 NUMBER IS TO BE PRINTED ON THE PLAN,
 FAC6115-23.002.
  
 2.)THE GIRDER/WALL CONNECTION (SHEET
 3) SPECIFIES HUGHES CONNECTORS; HUGHES
 IS NO LONGER IN BUSINESS.
  
 3.)THE WOOD CONSTRUCTION NOTES, ITEM
 #4, REFERS TO FBC3218.17.NOT IN THE
 FBC CODE BOOK.
  
 4.)HHGT1 AND HHGT2, CONNECTOR KST260
 SHEET RF1, NAILING CONFLICTS WITH
 CATALOG AND DESIGN UPLIFT ON THE PLAN
 EXCEEDS MAX ALLOWED BY THE CATALOT
 (USE THE GREY BAR WITHOUT STRESS
 INCRESE FOR STEEL, USP 2003 CATALOG).
 CHECK ALL CONNECTORS.
  
 5.)WOOD-TO-WOOD CONNECTORS ARE
 SPECIFIED IN WOOD-TO-MASONRY
 APPLICATIONS; FOR EXAMPLE, USP HTW.
 ADDRESS. (SHEET RF1).
  
 6.)PROVIDE A FIREBLOCK DETAIL FOR
 THE DROPPED CEILINGS/SOFFITS, FBC
 705.3, 2305.1.4.
  
 7.)STATEWIDE, LOCAL OR SITE
 SPECIFIC APPROVALS REQUIRED FOR WINDOWS,
 DOORS, TRUSS CONNECTORS, ROOF, SHUTTERS.
 FOR MORE INFORMATION ,
 WWW.FLORIDABUILDING.ORG.
  
 8.)ADDITIONAL FEES DUE (RADON).
  
 9.)REMOVE THE TITLE BLOCK FOR AFFINITI
 AS THEY ARE NOT THE DESIGNER OF
 RECORD.
  
 10.) SAFEGUARD (STORM SHUTTER SBCCI
 REPORT) IS NO LONGER IN BUSINESS.
 SUBMIT VALID PRODUCT APPROVALS.
  
 11.) THE ARCHITECTURALS ARE GARAGE
 LEFT, STRUCTURALS ARE GARAGE RIGHT.