Plan Review Notes
Plan Review Notes For Permit 03110095
Permit Number 03110095
Review Stop B
Sequence Number 3
Notes
Date Text
2004-04-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)RF1 AND THE MECHANICAL PAGE HAVE
 BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED.
  
 2.)IT IS UNCLEAR WHAT THE CHANGES
 ARE ON THE OTHER SHEETS SUBMITTED.ALL
 CHANGES ARE TO BE CLEARLY INDICATED
 WITH CLOUDS OR TRIANGLES.A NEW
 REVISION DATE IS GIVEN BUT I CAN'T
 LOCATE THE CHANGES.
  
 3.)SEPARATE PERMIT FOR SHUTTERS.
  
 4.)THE PRODUCT APPROVALS FOR THE
 CONNECTORS ARE DIFFICULT TO REVIEW.
 PLEASE PROVIDE A LIST OF THE CONNECTORS
 USED AND PROVIDE STATEWIDE PRODUCT
 APPROVAL FOR THOSE CONNECTORS.
  
 5.)THE CALCS SUBMITTED ARE LACKING
 THE INFORMATION REQUIRED BY FAC61G15-
 23.002.
  
 6.)SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION WAS SUBMITTED FOR THE ROYALL
 WALL PRODUCT.THE PAPERWORK WAS NOT IN
 COMPLIANCE FAC9B-72.HOWEVER, MY
 UNDERSTANDING IS THAT THIS PRODUCT CAN
 BE APPROVED UNDER FBC103.7.ADDRESS.
  
 7.)ADDITIONAL FEES DUE.IF THE
 OTHER REVISED SHEETS ARE RESUBMITTED,
 THIS IS A REVISION, NOT A SUBMITTAL.