2003-12-04 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE ENGINEER'S NAME AND LICENSE
 NUMBER IS TO BE PRINTED ON THE PLAN,
 FAC61G15-23.002.
  
 2.)THE GIRDER/WALL CONNECTION (SHEET
 3) SPECIFIES HUGHES CONNECTORS; HUGHES
 IS NO LONGER IN BUSINESS.
  
 3.)THE WOOD CONSTRUCTION NOTES, ITEM
 #4, REFERS TO FBC3218.17.NOT IN FBC
 CODE BOOK.
  
 4.)HHGT1 AND HHGT2, CONNECTOR KST260
 SHEET RF1, NAILING CONFLICTS WITH
 CATALOG AND DESIGN UPLIFT ON THE PLAN
 EXCEEDS MAX ALLOWED BY THE CATALOG
 (USE THE GREY BAR WITHOUT STRESS
 INCREASE FOR STEEL, USP 2003 CATALOG).
  
 5.)WOOD-TO-WOOD CONNECTORS ARE
 SPECIFIED IN WOOD-TO-MASONRY
 APPLICATIONS; FOR EXAMPLE, USP HTW.
 ADDRESS.(SHEET RF1).
  
 6.)PROVIDE A FIREBLOCK DETAIL FOR
 THE DROPPED CEILINGS/SOFFITS, FBC
 705.3, 2305.1.4.
  
 7.)STATEWIDE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 GARAGE DOOR
 GLASS BLOCK
 SHUTTERS
 TRUSS CONNECTORS
 FIXED WINDOW, NON IMPACT
 FIXED WINDOW, IMPACT
 PRINT THE COVER SHEET AND ATTACH TO
 THE NOA OR SBCCI REPORT.
  
 FOR CONNECTORS, PROVIDE A SCHEDULE
 WITH STATEWIDE PRODUCT APPROVAL
 NUMBERS.
  
 FOR MORE INFORMATION,
 WWW.FLORIDABUILDING.ORG
  
 8.)ARCHITECTURALS ARE FOR GARAGE L,
 STRUCTURALS AND SITE PLAN ARE FOR GARAGE
 RIGHT.
  
 9.)FEES DUE, $38.56 RADON, SEE
 ATTACHED BZ231387.
  
 10.) IF AFFINITI IS NOT THE DESIGNER
 OF RECORD AND ANOTHER ARCHITECT HAS
 SEALED THE PLAN, REMOVE AFFINITI'S TITLE
 BLOCK FROM THE PLAN.
  
 11.) SAFEGUARD (STORM SHUTTER SBCCI
 REPORT) IS NO LONGER IN BUSINESS. SUBMIT
 VALID PRODUCT APPROVALS FOR STORM
 SHUTTERS.