| Date |
Text |
| 2003-12-08 00:00:00 | ******PROVISO******* |
| | |
| | ADDRESS FOLLOWING CORRECTIONS BEFORE |
| | FRAMING INSPECTION. |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| 2003-12-03 00:00:00 | *****CORRECTIONS******* |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)THE ENGINEER'S NAME AND LICENSE |
| | NUMBER IS TO BE PRINTED ON THE PLAN, |
| | FAC61G15-23.002. |
| | |
| | 2.)THE GIRDER/WALL CONNECTION (SHEET |
| | 3) SPECIFIES HUGHES CONNECTORS; HUGHES |
| | IS NO LONGER IN BUSINESS. |
| | |
| | 3.)THE WOOD CONSTRUCTION NOTES, ITEM |
| | #4, REFERS TO FBC3218.17.NOT IN THE |
| | FBC CODE BOOK. |
| | |
| | 4.)HHGT1 AND HHGT2, CONNECTOR KST260 |
| | SHEET RF1, NAILING CONFLICTS WITH |
| | CATALOG AND DESIGN UPLIFT ON THE PLAN |
| | EXCEEDS MAX ALLOWED BY THE CATALOG |
| | (USE THE GREY BAR WITHOUT STRESS |
| | INCREASE FOR STEEL, USP 2003 CATALOG). |
| | |
| | 5.)WOOD-TO-WOOD CONNECTORS ARE |
| | SPECIFIED IN WOOD-TO-MASONRY |
| | APPLICATIONS; FOR EXAMPLE, USP HTW. |
| | ADDRESS.(SHEET RF1). |
| | |
| | 6.)PROVIDE A FIREBLOCK DETAIL FOR |
| | THE DROPPED CEILINGS/SOFFITS, FBC |
| | 705.3, 2305.1.4. |
| | |
| | 7.)STATEWIDE, LOCAL OR SITE SPECIFIC |
| | PRODUCT APPROVALS REQUIRED FOR THE |
| | FOLLOWING: |
| | GARAGE DOOR |
| | GLASS BLOCK |
| | SHUTTERS |
| | TRUSS CONNECTORS |
| | FIXED GLASS WINDOW |
| | |
| | PROVIDE A TRUSS CONNECTOR LIST WITH |
| | ALL APPROVAL NUMBERS. |
| | |
| | FOR MORE INFORMATION, |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 8.)ADDITIONAL FEES DUE (RADON), |
| | SEE ATTACHED BZ233271. |
| | |
| | 9.)REMOVE THE TITLE BLOCK FOR |
| | AFFINITI FROM THE PLAN AS THEY ARE |
| | NOT THE DESIGNER OF RECORD. |
| | |
| | 10.) SAFEGUARD (STORM SHUTTER SBCCI |
| | REPORT) IS NO LONGER IN BUSINESS. SUBMIT |
| | VALID PRODUCT APPROVALS FOR STORM |
| | SHUTTERS. |