Plan Review Notes
Plan Review Notes For Permit 03110094
Permit Number 03110094
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-08 00:00:00******PROVISO*******
  
 ADDRESS FOLLOWING CORRECTIONS BEFORE
 FRAMING INSPECTION.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
2003-12-03 00:00:00*****CORRECTIONS*******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE ENGINEER'S NAME AND LICENSE
 NUMBER IS TO BE PRINTED ON THE PLAN,
 FAC61G15-23.002.
  
 2.)THE GIRDER/WALL CONNECTION (SHEET
 3) SPECIFIES HUGHES CONNECTORS; HUGHES
 IS NO LONGER IN BUSINESS.
  
 3.)THE WOOD CONSTRUCTION NOTES, ITEM
 #4, REFERS TO FBC3218.17.NOT IN THE
 FBC CODE BOOK.
  
 4.)HHGT1 AND HHGT2, CONNECTOR KST260
 SHEET RF1, NAILING CONFLICTS WITH
 CATALOG AND DESIGN UPLIFT ON THE PLAN
 EXCEEDS MAX ALLOWED BY THE CATALOG
 (USE THE GREY BAR WITHOUT STRESS
 INCREASE FOR STEEL, USP 2003 CATALOG).
  
 5.)WOOD-TO-WOOD CONNECTORS ARE
 SPECIFIED IN WOOD-TO-MASONRY
 APPLICATIONS; FOR EXAMPLE, USP HTW.
 ADDRESS.(SHEET RF1).
  
 6.)PROVIDE A FIREBLOCK DETAIL FOR
 THE DROPPED CEILINGS/SOFFITS, FBC
 705.3, 2305.1.4.
  
 7.)STATEWIDE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 GARAGE DOOR
 GLASS BLOCK
 SHUTTERS
 TRUSS CONNECTORS
 FIXED GLASS WINDOW
  
 PROVIDE A TRUSS CONNECTOR LIST WITH
 ALL APPROVAL NUMBERS.
  
 FOR MORE INFORMATION,
 WWW.FLORIDABUILDING.ORG
  
 8.)ADDITIONAL FEES DUE (RADON),
 SEE ATTACHED BZ233271.
  
 9.)REMOVE THE TITLE BLOCK FOR
 AFFINITI FROM THE PLAN AS THEY ARE
 NOT THE DESIGNER OF RECORD.
  
 10.) SAFEGUARD (STORM SHUTTER SBCCI
 REPORT) IS NO LONGER IN BUSINESS. SUBMIT
 VALID PRODUCT APPROVALS FOR STORM
 SHUTTERS.