Plan Review Notes
Plan Review Notes For Permit 03110081
Permit Number 03110081
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT M1 INDICATES THAT A NEW TOILET
 ROOM WILL BE ADDED, BUT THE FLOOR PLAN
 DOES NOT INDICATE THIS. PLEASE CLAIRFY.
 2) DRINKING FOUNTAIN IS NOT SHOWN ON THE
 NEW FLOOR PLAN. DRINKING FOUNTAIN IS RE-
 QUIRED PER TABLE 403.1. (ALSO SEE 410.1)
 IT SEEMS THAT THE D/F WAS REMOVED WHEN
 FLOOR PLAN WAS DEMOED. PLEASE CLAIRFY.
 IF NEW D/F SUBMIT DETIAL SHOWING COMPLI-
 ANCE WITH 11-4.15 AND ALL SUBSECTIONS &
 SECTION 11-4/1/3(10)(A) FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 3) ALL CAPPED PLUMBING LINES SHALL BE
 INSPECTED PRIOR TO COVERING.
 4) SIGNATURE REQUIRED ON SEAL OF ENGIN-
 EER PER FAC 61G15-23.001(1) & FS471.025
 ALSO ENGINEERS NAME AND LICENSE NUMBER
 IS REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002(2) & FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]