| Plan Review Notes For Permit 03110081 |
| Permit Number |
03110081 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-10 00:00:00 | DENIED: | | | 1) | | | PLEASE NOTE PER FS 471.025 & FAC 61G15- | | | 23.002, PLANS SHALL BE SIGNED, SEALED | | | AND DATED BY THE ENGINEER.PER THE | | | BOARD OF PROFFESIONAL ENGINEERS, PLANS | | | ARE TO BE SIGNED AND NOT INITIALED. | | | PLEASE CORRECT. | | | | | | 2) | | | PLEASE INDICATE ANY EXISTING DUCT SMOKE | | | DETECTORS.SYSTEMS WITH THE DESIGN | | | CAPACITY GREATER THAN 2,000 OR COMBINED | | | DESIGN CAPACITY SHALL HAVE DUCT SMOKE | | | DETECTORS WITH NOTIFICATION TO ALARM/ | | | STROBE. | | | | | | 3) | | | NOTE 6 IS NOT LISTED IN THE SPECIFIC | | | NOTES, SHOULD THIS READ NOTE 5? | | | | | | 4) | | | PLEASE CLARIFY OUTSIDE AIR REQUIREMENTS | | | FOR THE CONFERENCE ROOMS. PER 2001 | | | FBC(M) TABLE 403.3 & ASHRAE 62-89 THE | | | REQUIRED CFM PER PERSON SHOULD BE A | | | MINIMUM OF 20 CFM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|