Plan Review Notes
Plan Review Notes For Permit 03110081
Permit Number 03110081
Review Stop M
Sequence Number 1
Notes
Date Text
2003-12-10 00:00:00DENIED:
 1)
 PLEASE NOTE PER FS 471.025 & FAC 61G15-
 23.002, PLANS SHALL BE SIGNED, SEALED
 AND DATED BY THE ENGINEER.PER THE
 BOARD OF PROFFESIONAL ENGINEERS, PLANS
 ARE TO BE SIGNED AND NOT INITIALED.
 PLEASE CORRECT.
  
 2)
 PLEASE INDICATE ANY EXISTING DUCT SMOKE
 DETECTORS.SYSTEMS WITH THE DESIGN
 CAPACITY GREATER THAN 2,000 OR COMBINED
 DESIGN CAPACITY SHALL HAVE DUCT SMOKE
 DETECTORS WITH NOTIFICATION TO ALARM/
 STROBE.
  
 3)
 NOTE 6 IS NOT LISTED IN THE SPECIFIC
 NOTES, SHOULD THIS READ NOTE 5?
  
 4)
 PLEASE CLARIFY OUTSIDE AIR REQUIREMENTS
 FOR THE CONFERENCE ROOMS. PER 2001
 FBC(M) TABLE 403.3 & ASHRAE 62-89 THE
 REQUIRED CFM PER PERSON SHOULD BE A
 MINIMUM OF 20 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved