Plan Review Notes For Permit 03110081
Permit Number 03110081
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-04 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE REQ'D
 TO BE SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD. PER FAC 61G15-23.002
 AND FS 471
 PLEASE SEE THAT THIS IS REQ'D FOR ALL
 TRADES WEATHER OR NOT COMMENT IS MADE.
  
 2)NOTE: PLEASE SEE THAT PANEL SCHEDULES
 ARE VERY FAINT AND NOT CLEAR. PLEASE
 DARKEN IN ORDER TO READ.
  
 3)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 AT 125% 215.3/ 230.42 ETC.
  
 PLEASE SEE COMMENTS FROM ALL OTHER
 REVIEWERS AS THEY MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 4)NOTE: PLEASE CLARIFY REQ'D SIGN
 CIRCUIT PER 600-5. UNABLE TO READ ON
 PANEL SCHEDUL.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE OLD SET MAY BE SUBMITTED FOR REF
 ONLY AND MAY BE REQ'D BY OTHER REVIEWERS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]