| 2003-11-04 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE THAT PLANS ARE REQ'D | | | TO BE SIGNED, DATED AND SEALED BY THE | | | ENGINEER OF RECORD. PER FAC 61G15-23.002 | | | AND FS 471 | | | PLEASE SEE THAT THIS IS REQ'D FOR ALL | | | TRADES WEATHER OR NOT COMMENT IS MADE. | | | | | | 2)NOTE: PLEASE SEE THAT PANEL SCHEDULES | | | ARE VERY FAINT AND NOT CLEAR. PLEASE | | | DARKEN IN ORDER TO READ. | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125% 215.3/ 230.42 ETC. | | | | | | PLEASE SEE COMMENTS FROM ALL OTHER | | | REVIEWERS AS THEY MAY HAVE AN AFFECT | | | ON ELECTRICAL PLANS. | | | | | | 4)NOTE: PLEASE CLARIFY REQ'D SIGN | | | CIRCUIT PER 600-5. UNABLE TO READ ON | | | PANEL SCHEDUL. | | | | | | PLEASE REMOVE ALL OLD VOIDED SHEETS AND | | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | ONE OLD SET MAY BE SUBMITTED FOR REF | | | ONLY AND MAY BE REQ'D BY OTHER REVIEWERS | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|