| 2004-04-16 00:00:00 | ************ UNSAT *************** |
| | |
| | PLEASE SEE COMMENTS BELOW AND ALL PREVI- |
| | -OUS COMMENTS. PLEASE CALL IF THERE ARE |
| | ANY QUESTIONS, OR IF A MEETING CAN BE |
| | SET UP TO GO OVER PLANS AND COMMENTS. |
| | PREVIOUS REVIEWS GAVE # FOR QUESTIONS. |
| | |
| | 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU'S AND 10KW HEAT. A MIN OF 125% |
| | IS REQ'D. PLANS INDICATE 50A OCP FOR |
| | ALL THREE UNITS. |
| | |
| | 2)NOTE: PLEASE SEE SERVICE RISER, |
| | PLEASE INDICATE METERCAN SIZE/AMPERAGE. |
| | PLEASE SEE RISER NOW SHOWS WHAT APPEARS |
| | TO BE A MAIN DISC? LOAD CALCS MENTION |
| | A 400A SERVICE, BUT MAIN DOES NOT INDI- |
| | -CATE THIS. SERVICE ENT CONDUCTORS ARE |
| | SHOWN AS 2/0'S, WHICH ARE ONLY RATED FOR |
| | A 200A SERVICE. PLEASE SEE 310.15B6 FOR |
| | MIN SIZE FOR 400A SERVICE. |
| | |
| | 3)NOTE: PLEASE SEE RISER, WHAT APPEARS |
| | TO BE A RISER MAIN DOES NOT LIST OR |
| | INDICATE OCP/BRKRS TO SUB-FEED OF EACH |
| | 200A PANELS. IF THIS IS A 400A SERVICE, |
| | WHERE IS THE OCP FOR 2/0'S TO EACH PANEL |
| | AND PANELS RATED FOR 200A'S??? |
| | |
| | THIS IS ONLY A NOTE: PANELS ARE SHOWN AS |
| | MCB. PANELS SHOULD BE FED W/ OCP, MCB |
| | ARE NOT REQ'D BUT MAY BE INSTALLED. |
| | IF SHOWN ON PLANS THEN THEY WILL BE |
| | REQ'D TO BE INSTALLED. |
| | |
| | 4)NOTE: PLEASE SIZE GROUNDING ELECTRODE |
| | CONDUCTOR FOR 400A SERVICE. 250.66,310. |
| | 15B6. 1/0 MIN. |
| | |
| | 5)NOTE:PLEASE LABEL PANELS. PLEASE |
| | ALSO SEE RISER INDICATES 2/0'S FOR |
| | ONE PANEL BUT NOT THE OTHER. |
| | PLANS ONLY SHOW A METERCAN ON OUTSIDE OF |
| | HOUSE. |
| | |
| | NEW NOTE: |
| | 6)NOTE: PLEASE INDICATE REQ'D LT/RECEPTS |
| | FOR AHU'S. 210.70/ 210.63 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | PLEASE SEE ATTACHED COPY OF FS 553.80(2) |
| | (B). THIS NOTICE IS GIVEN TO THE DESIGN |
| | PROFESSIONAL FOR PLANS FOR NEXT REVIEW. |