| Notes |
| Date |
Text |
| 2004-06-01 00:00:00 | BUILDING DENIED | | | | | | 1)SUBMIT STATE OR LOCAL PRODUCT APPROVAL | | | FOR THE FOLLOWING: | | | - THREE PANEL SLIDING GLASS DOOR | | | - SOLID CORE OUTSWING DOOR AT GARAGE | | | - STRUCTURAL WINDOW MULLIONS (IMPACT) | | | | | | 2) THE STATE PRODUCT APPROVAL FOR THE | | | WOOD FRENCH DOORS IS LISTED AS PENDING. | | | AN APPROVED STATUS IS REQUIRED BEFORE A | | | C.O. WILL BE ISSUED OR LOCAL PRODUCT | | | APPROVAL CAN BE APPLIED FOR. | | | | | | 3) THE STRUCTURE IS LOCATED IN AN "A5" | | | FLOOD ZONE, AN ELEVATION CERTIFICATE | | | WILL BE REQUIRED. THE LOWEST FLOOR | | | ELEVATION IS REQUIRED TO BE 6" ABOVE | | | BASE FLOOD ELEVATION PER CITY OF WPB | | | MUNICIPLE CODE. | | | | | | 4) ENGINEERED HAMBRO FLOOR SYSTEM | | | DRAWINGS ARE TO BE REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD. HAVE THEM | | | STAMPED AND SIGNED BY HIM AS REVIEWED | | | AND ACCEPTED. | | | | | | 5) SUBMIT THE INSTALLATION MANUAL FOR | | | THE HAMBRO FLOOR SYSTEM. | | | | | | 6) THE ORIGIONAL PERMIT APPLICATION IS | | | NOT WITH THIS RESUBMITTAL. ADDITIONAL | | | FEES WILL BE REQUIRED TO ADD SUBS TO | | | THIS PERMIT OR SEPARATE PERMITS WILL BE | | | REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|