| Date |
Text |
| 2004-03-03 00:00:00 | ************* UNSAT ************* |
| | |
| | 1)NOTE : PLANS NOW HAVE TITLE BLOCK |
| | REMOVED. HOWEVER, PLANS ARE STILL REQUI- |
| | -RED TO BE SIGNED BY THE PERSON EAL |
| | RESPONSIBLE FOR THE PLANS. 104.2.1 FBC |
| | IF ITS AN ARCH/ENGINEER, THEN SIGNED, |
| | DATED AND SEALED ALONG WITH THE TITLE |
| | BLOCK. |
| | FS 471/481, 61G15-23.002, 61G1-16.004 |
| | |
| | 2)NOTE: PLEASE SEE PLANS NOW HAVE |
| | PANEL SCHEDULE AS REQUESTED ON FIRST |
| | REVIEW, HOWEVER, PLEASE SEE THE FOLLOW- |
| | -ING COMMENTS. ALSO, SOME COMMENTS FROM |
| | FIRST REVIEW ARE NOT CLEAR. |
| | |
| | 3)NOTE: PLEASE SEE PLANS, ONLY SHOWS A |
| | METER ON THE OUTSIDE OF HOUSE. RISER |
| | SEEMS TO INDICATE TWO MCB PANELS OUTSIDE |
| | ?? AND SHOWS TWO 2" CONDUITS FROM TOP TO |
| | INSIDE PANELS?? PLEASE CORRELATE PLANS. |
| | ONLY TWO PANEL SCHEDULES ARE SUBMITTED. |
| | |
| | 4)NOTE: PLEASE ALSO SEE PANELS SCHEDULES |
| | SUBMITTED, THEY ARE NOW SHOWN AS 400A |
| | MCB PANELS, WHICH WOULD MAKE THE SERVICE |
| | 800A'S?? RISER SHOWS AS 200A EACH?? |
| | PLEASE CORRELATE AND INDICATE AMPERAGE |
| | OF METERCAN. |
| | |
| | 5)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU'S/HEAT. PLEASE SEE PANEL "B", |
| | SHOWS 30A OCP FOR 10KW HEAT.? |
| | PLEASE CORRELATE PANEL SCHEDULES AND |
| | LOAD CALCULATIONS. |
| | |
| | 6)NOTE: PLEASE SEE SM APPL LOADS SHOWN |
| | ON LOAD CALCULATIONS. ONLY SHOWS TWO,YET |
| | PANEL SCHEDULES INDICATE 4. PLEASE SEE |
| | 220.16, 1500VA FOR EACH SM APPL. |
| | |
| | 7)NOTE: PLANS INDICATE A GAS POOL HEATER |
| | AND LOAD CALCAULTIONS SHOWS ELECTRICAL |
| | POOL HEATER?? PLEASE ALSO SEE PANEL |
| | SCHEDULES DO NOT INDICATE POOL HEATER?? |
| | |
| | 8)NOTE: PLEASE CLARIFY TWO WHIRLPOOL |
| | TUBS. FLOOR PLANS ONLY SHOW ONE. |
| | PLEASE CORRELATE. |
| | |
| | 9)NOTE: PANEL SCHEDULES INDICATE 45 CIR |
| | PANELS?? ALSO INDICATE ALL CIRCUITS ON |
| | RIGHT HAND SIDE AFTER (30) BEING THE |
| | SAME CIRCUIT #'S ON EACH SIDE??? |
| | |
| | 10)NOTE: PLEASE SEE WHIRLPOOL TUB ON |
| | PLANS, DO NOT INDICATE A GFI RECEPT.?? |
| | |
| | PLEASE CORRELATE PLANS AND ADDRESS THE |
| | ABOVE COMMENTS. PLEASE SUBMIT FOR REVIEW |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |