| 2004-01-21 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLANS WERE SUBMITTED FOR PLAN |
| | REVIEW ON FIRST REVIEW AND CONTAINED A |
| | TITLE BLOCK FOR AN ENGINEER. PLANS HAVE |
| | SINCE COME BACK AND DO NOT CONATIN ANY |
| | INFORMATION FOR PLAN/DESIGN. AS REQ'D |
| | UNDER FBC 104.2.1 |
| | PLANS ARE NOT REQ'D TO BE SIGNED AND |
| | SEALED UNLESS CONTAINING A TITLE BLOCK |
| | AND WERE DONE BY AN ARCH/ENG. |
| | PLANS STILL MUST BE NAMED AND SIGNED |
| | BY PERSON RESPONSIBLE FOR PLAN. |
| | |
| | 2)NOTE: PLEASE SEE SERVICE, SHOWN AS |
| | 400A SERVICE. SHOWS 42CIR MCB PANELS |
| | FEEDING SOME OTHER PANELS. PLANS ONLY |
| | SHOW TWO PANELS IN GARAGE AND NO MCB |
| | PANELS OUTSIDE WITH METER, AS RISER SHOW |
| | -S. PLEASE SEE FIRST SET OF NOTES |
| | ASKING FOR PANEL SCHEDULES. |
| | |
| | 3)NOTE: PLEASE SEE 210.52D,210.11C3 FOR |
| | MIN REQ'D FOR BATH RECEPTS. SEE RECEPTS |
| | MISSING FROM BATH(S). PLEASE LIST AS REQ |
| | 'D. |
| | |
| | 4)NOTE: PLEASE SEE MISSING LT FOR BATH |
| | DOWNSTAIRS NEXT TO MEDIA/BEDRM. |
| | 210.70 |
| | |
| | 5)NOTE: PLEASE SEE PLANS, PLEASE CLARIFY |
| | LOCATION OF AHU`S AND DISC'S. 440.11 |
| | |
| | 6)NOTE: PLEASE SIZE GROUNDING ELECTRODE |
| | CONDUCTOR PER 250.66 |
| | 310.15B6 REQ'S MIN 400MC TOTAL FOR |
| | SEC'S, 250.66 SIZES GEC FOR 400MCM/ |
| | WOULD BE 1/0. |
| | |
| | 7)NOTE: PLEASE SEE GFI NOTE ABOVE RISER, |
| | SHOWS GFI W/IN 15' OF POOL. PLEASE SEE |
| | 680.22A5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |