| Plan Review Notes For Permit 03110048 |
| Permit Number |
03110048 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-03 00:00:00 | DENIED; | | | 1.PLANS ARE NOT SIGNED OR SEALED. | | | 2.PLUMBING RISER DIAGRAM DOES NOT MATCH | | | FLOOR PLAN. | | | A.MASTER BATH AND LAUNDRY ROOM ARE | | | ON THE 1ST FLOOR ON FLOOR PLAN A-3 | | | RISER DIAGRAM SHOWS 2ND FLOOR. | | | B.LAUNDRY TUB CANNOT BE ON SAME | | | STACK AS W/M BECAUSE FIXTURES ARE | | | ON DIFFERENT SIDES OF ROOM. | | | C.BUTLER PANTRY SINK NOT ON RISER | | | DIAGRAM. | | | D.HIS BATHROOM HAS SHOWER NOT TUB. | | | E.RISER DIAGRAM SHOULD BE AN IMAGE | | | OF THE FLOOR PLAN, FIXTURES ARE | | | NOT IN PROPER ORDER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|