| 2003-11-07 00:00:00 | *************** UNSAT **************** |
| | |
| | PLEASE SEE THAT PLANS ARE ONLY IN FOR |
| | PLAN REVIEW AND NOT SUBMITTED FOR |
| | PERMIT AT THIS TIME. |
| | |
| | 1)NOTE: PLANS WILL BE REQ'D TO BE SIGNED |
| | DATED AND SEALED BY THE ARCH/ENGINEER |
| | OF RECORD PER FS 471.025,481.221 |
| | PLEASE NOTE: FBPE'S HAS GIVEN TO THIS |
| | OFFICE INFORMATION THAT REQUIRES A |
| | SIGNATURE THAT CONTAINS A MIN IF FIRST |
| | AND LAST NAME. |
| | |
| | 2)NOTE: PLEASE SEE PLANS, SHOWS BOTH |
| | PANEL IN GARAGE? PLEASE CLARIFY WHERE |
| | METER LOCATION IS. PLEASE SEE LOCAL |
| | AMENDMENTS, 210.70 NO MORE THAT 8' OF |
| | UNPROTECTED CONDUCTOS INSIDE HOUSE. |
| | |
| | 3)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) |
| | WITH CIRCUITS, AWG AND OCP REQ'D. 215.5 |
| | PLEASE LIST THE REQUIRED ARC FAULT |
| | PROTECTTION PER NEC 2002 210.12 |
| | PLEASE LIST BATH(S) AS PER 210.52D AND |
| | 210.11C3 AS 20A AND #12. ETC ETC |
| | |
| | 4)NOTE: PLEASE SEE PLANS SHOW 4 A/C COND |
| | UNITS AND PLEASE SHOW AHU'S AND DISC PER |
| | 440.11 |
| | |
| | 5)NOTE: PLEASE SEE 210.52E FOR MIN OF |
| | FRONT AND REAR GFI RECEPTS. |
| | |
| | 6)NOTE: PLEASE SEE 210.52 FOR RECEPTS |
| | REQUIRED FOR WALL SPACE, INCLUDING |
| | RAIL AREAS. THERE IS MANY RECEPTS MISS- |
| | ING UPSTAIRS. |
| | |
| | 7)NOTE: PLEASE SEE NFPA-72 8-1.4.2, |
| | SD'S ARE NOT PERMITTED IN KITCHENS AND |
| | INFACT MUST BE A MIN OF 3' FROM KITCHENS |
| | AND BATHS. |
| | PLEASE ALSO SEE THAT A SD IS REQ'D AT |
| | THE BASE OF STAIRS LEADING TO THE FLOOR |
| | ABOVE IN THE IMMEDIATE VICINITY OF STAIR |
| | -S. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |