| 2003-12-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHTS A-1 & A-3 SHOW TURNING RADIUS IN | | | TOILET ROOMS. 11-4.22.3 | | | 2) SHT A-1 & A-3 DOORS SHALL NOT SWING | | | INTO THE CLEAR FLOOR SPACE REQUIRED FOR | | | ANY FIXTURE. | | | 3) SHTS A-1 & A-3 SHOW CLEAR FLOOR SPACE | | | FOR BREAK ROOM SINK. | | | 4) SHT A-3 SUBMIT A DETAIL FOR DRINKING | | | FOUNTAIN SHOWING WITH 11-4.15 AND ALL | | | SUBSECTIONS. | | | 5) SHT P0.1 DOMESTIC WATER ISOMETRIC. | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE | | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | AND MANUF INSTALLATION INSTRUCTIONS. | | | 6) SHTS P0.1 & P2.1 SANT. RISER AND | | | FLOOR PLAN. BREAK ROOM SINK SHALL TIE IN | | | DOWNSTREAM OF BATHROOM FIXTURES. 909.1 | | | 7) SIGNATURE REQUIRED ON SEAL PER FAC | | | 61G15-23.002(1). INITALS NOT APPROVED | | | PER BUILDING OFFICIAL & FBPE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|